511392
301AP User Manual
21
2/07
Honeywell
Specifications
Technical Specifications
Specifications
Technical Specifications
Power requirements:
17 - 27 Vac, 24 - 38 Vdc, 200 mA @ 24 Vdc,
Relays
3 DPDT relays
Relay output rating:
5 A, 30 Vdc or 250 Vac (resistive load)
Communication cable RS-485 two twisted/shielded wires 24 AWG
Length of conductors: Up to 600 m (2000 ft.) per
channel
T-Tap: 20 m (65 ft.) maximum per t-tap
40 m (130 ft.) total
Communication :
RS-485 ModBus
Operating humidity
range:
0-95% RH, non-condensing
Operating
temperature range:
0 to 40ºC (32 to 104ºF)
Audible alarm:
65 dB at 1 m (3 feet)
Visual indicators:
Alarm A: red LED
Alarm B: red LED
Alarm C: red LED
Power: green LED
Fault: yellow LED
Tx: yellow LED
Display:
Alphanumeric backlight liquid crystal display (LCD)
Dimensions
:
20.3 x 28 x 5.7 cm (H x W x D)
(8 x 11 x 2.15 in.)
Weight:
1.58 kg (3.5 lbs.)
Housing rating:
NEMA 4X, ABS polycarbonate indoor
Certifications:
CSA C22.2 no. 205-M1983
UL 1244