5. Internal Memory Configuration and Functions
5.2. Internal memory functions
84
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
The flag can be set for the input variation in terms of quantity as well as rate of change.
Figure 30 – Rate of change alarm flag
Temperature value (internal memory address %UWa.b.4 ~7)
1.
Temperature-converted (measured temperature) value of each channel is stored as
shown below.
Figure 31 – Temperature-converted value
Address
Description
%UWa.b.4
CH0 Temperature Value
%UWa.b.5
CH2 Temperature Value
%UWa.b.6
CH2 Temperature Value
%UWa.b.7
CH3 Temperature Value
2.
Range of the output (measured) temperature value based on sensor type is as
follows:
Sensor
type
Output range
Effective measuring range Remarks
Pt100
2100 – 8600
(-210.0°C – 860.0°C)
2000 – 8500
(-200.0°C – 850.0°C)
_