5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
104
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
5.
Use I/O parameter window for more convenient setting.
Figure 57 – I/O parameter window 11 (RCA type)
Input variation alarm upper/lower limit value (addresses 48–55)
1.
The default range of values is ‘-1000 to 1000’ as shown below. If the set value is
outside the range, then setting error will occur with the setting value of ‘0’ saved
inside the module.
2.
If input variation range is set in the input variation alarm type, it will be a
percentage value of input variation rate specified to the first decimal point.
3.
If input variation value is set in the input variation alarm type, the unit of the value
to be set in this area represents temperature variation.
Figure 58 – Input variation alarm maximum/minimum value