TAKING CARE OF UNEXPECTED PROBLEMS
86
NO POWER AT THE DC TERMINALS
ENGINE AUTOMATICALLY STOP AND THE CO ALARM INDICATOR FLASHING
ENGINE AUTOMATICALLY STOP AND THE FAULT/CO SENSOR LIFE
INDICATOR FLASHING
FAULT/CO SENSOR LIFE INDICATOR FLASHING WHEN RUNNING THE
ENGINE
Possible Cause
Correction
DC circuit protector OFF.
Turn DC circuit protector ON
(see page 32).
Faulty generator.
Take the generator to an authorized
Honda Power Equipment dealer, or
refer to the shop manual.
Possible Cause
Correction
CO concentration around the
generator is high.
Review the location of the generator,
and place it in a well-ventilated
outdoor location (see page 26).
When the engine is stopped
automatically by CO-MINDER, press
the CO-MINDER reset button to restart
the engine (see page 49).
Possible Cause
Correction
CO sensor malfunction.
If the engine cannot be started and
the CO ALARM indicator flashes, even
if the location of the generator has
changed, there may be a CO-MINDER
malfunction. Consult an authorized
Honda Power Equipment dealer.
CO sensor may have reached the end
of its useful lifespan (see page 27).
Consult an authorized Honda Power
Equipment dealer.
Possible Cause
Correction
CO sensor may reach the end of its
useful lifespan (see page 27).
Consult an authorized Honda Power
Equipment dealer for replacement.