709D-VmA and 709E-VmA Series

Electronic Fan Speed Controllers

Hoffman

|

Controls

Installation & Operating

Instructions

1

Introduction

The 709 Series of Electronic Fan Speed Controllers consists of two 

models. These 2 models allow for the option of deriving power 

for the control via an external 24 VAC transformer (provided 

by customer), or directly from line and phase of the “onboard” 

PCB mounted transformer. The 709D does not include the 24 

VAC transformer. The 709E includes the transformer internally 

connected to the line voltage.
Each of these models have the option of using a Hoffman Controls   

Proportional Integration (PI) Interface plug-in PCB assembly. 

This document contains instructions for establishing the electrical 

connections for each of the 709 Series controllers’ four configura-

tions.
The 709E controller has sufficient VA (power) to drive the 

optional Proportional Integration (PI) Interface plug in card and 

one of the the following signal sources; a Hoffman Controls 203-

5(24)V Flow Transducer,  a 203-6(24)P Pressure Transducer, or a 

906VmA Thermostat. IMPORTANT: When using 709D series 

controllers, select a transformer to meet the requirements of all the 

components being used.

Initial Controller Installation

Motor Line Voltage Wiring (Figures 1 & 2)

Connect one side of the motor to the "LOAD" terminal on the 

709D PCB.  Connect the other side of the motor to L1. 
Connect L2 or Neutral to the "LINE" terminal on the 709D PCB 

assembly.

24 Volt Wiring (Figures 1&2)

Connect the primary side of the 24 VAC transformer to the same 

L1 & L2 or Neutral as the motor.

The primary of this external 24 VAC transformer MUST BE THE 

SAME PHASE that is supplying power to the motor.

Connect the leads of the 24 VAC transformer secondary to the 

"24V IN" & adjacent "GND" terminals of the 709 PCB assembly. 

The GND terminal allows for a grounded secondary of the 24 volt 

transformer if required. 

Do not share this AC GND with DC signal 

sources, use a separate wire connection for dc signal ground.

Control Signals (Figure 1)

The 709D accepts industry standard 2-10 VDC or 4-20 ma input 

signals.  Connect the 2-10 VDC or 4-20 mA control signal and 

it's GND reference to their respective terminal block locations.
There is a common signal GND shared by both VDC and mA. 

PI Interface Option (Figure 2)

IMPORTANT: The PI Interface Option will replace the standard 

2-10 VDC and 4-20 mA inputs on the 709D control. When using 

this option the control signals are connected to their respective 

terminals on the PI Interface PCB, not the 709 PCB terminals.

Insure that all power sources have been disconnected. 
Remove longer top cover of 709D or E (with B or C suffix) model 

controller by removing (4) self-tapping screws.
Secure the controller via the heat sink mounting tabs.
Connect the green wire to earth ground.

709D Wiring

Transformer Phasing

The model 709D Series Electronic Fan Speed Control requires an 

external 24 VAC source. 

This 24 VAC SOURCE MUST BE IN 

PHASE with the line voltage being supplied to the motor

. Motor 

line voltage and transformer primary MUST be on the same 

phase/lines.

709E Wiring

Transformer Phasing

The model 709E Electronic Fan Speed Control contains an inter-

nal transformer to provide the required 24 VAC that is "in phase" 

when the speed control is required to function.

Motor Wiring (Figures 3 & 4)

Connect one side of the motor to the "LOAD" terminal on the 

709E PCB. Connect the other side of the motor to L1.

Power Supply (Figures 3 & 4)

Connect L2 or Neutral to the "LINE" terminal on the 709E 

PCB.  Connect L1 to the 120 VAC or 208-240 VAC terminal as is 

appropriate for the voltage required.

Control Signals (Figure 3

)

The 709E accepts industry standard 2-10 VDC or 4-20 mA input 

signals.  Connect the 2-10 VDC or 4-20 mA control signal to 

their respective terminal block.
There is a common signal GND shared by both VDC and mA. 

PI Interface Option (Figure 4

)

IMPORTANT: The PI Interface Option will replace the standard 

2-10 VDC and 4-20 mA inputs on the 709E control. When using 

this option the control signals are connected to their respective 

terminals on the PI interface PCB, not the 709 PCB terminals.

PI Interface Options

The 709 series of controllers have an available PI Interface option. 

The PI Interface will allow for two modes of fan speed control in 

relation to a setpoint.
In the Direct Acting or "DA" mode, the PI Interface does not 

provide an input to the 709 series control until a control signal has 

exceeded the setpoint level.
In the Reverse Acting or "RA" mode, The PI interface will contin-

uously provide an input to the 709 series control in an attempt to 

maintain a control signal at the setpoint level.
Refer to the Hoffman Controls PI Interface Product Data Sheets, 

PI Interface Installation & Operation Instructions, or Application 

Notes literature for complete details on the operation of the 

optional PI Interface board.