Installation 19
HIT-4L
HP-329
Flowmeter Input
The flowmeter input accepts a low-level sinusoidal signal from a
magnetic type pickup coil, contact closure or DC pulse signal. An
optional circuit board (PCA193) provides an input that will accept a
signal from MCP/RF type pickups. Switches 1,2,3,4,5,6 on SW-1 must
be set according to the type of pickup coil to be used.
SW-1 SWITCH SETTINGS FOR FLOWMETER INPUT OPTIONS
INPUT OPTION
PCA192
SW-1 SETTINGS
Magnetic pickup
Contact Closure
1,2,3 - ON
4,5,6 - OFF
1 2 3 4 5 6
RediPulse
TTL
1,2,3,5 - OFF
4,6 - ON
1 2 3 4 5 6
RediPulse
Open Collector
*
MCP/RF
1,2,3,6 - OFF
4,5 - ON
1 2 3 4 5 6
*
PCA193 is required and J2 must be equipped for MCP/RF
3.1
4-20 mA Current Loop
When powered from a two-wire 4-20 mA current loop, a minimum
supply voltage in the range of 8-30 Volts DC is required, depending on
the loop load resistance. At nominal 250 Ohms loop resistance the
minimum power supply is 13V.
Backup batteries are included to ensure that volume accumulation will
not be interrupted during a power failure.
Summary of Contents for HIT-4L
Page 2: ......
Page 30: ...24 Installation HP 329 HIT 4L This page intentionally left blank...
Page 42: ...Operation 36 HP 329 HIT 4L This page intentionally left blank...
Page 52: ...HIT 4 Communication Program 46 HP 329 HIT 4L This page intentionally left blank...
Page 68: ...62 HIT 4 Communication Program HP 329 HIT 4L This page intentionally left blank...
Page 71: ...Appendix A Declaration of Conformity 65 HIT 4L HP 329 APPENDIX A DECLARATION OF CONFORMITY...
Page 72: ...66 Appendix A Declaration of Conformity HP 329 HIT 4L...