  INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

                                                                                         

 

Hochiki America Corporation 
7051 Village Drive, Suite 100 
Buena Park, CA 90621-2268 
 

DWG # HA-06-060, Rev 11/21 
PAGE 1 of 2 
PART # 1700-09987 
 

Conventional Detectors and Bases 

BASE SPECIFICATIONS 

MODEL 

Base 
ID 

Compatible 
Detector ID 

Alarm Current 

Mounting Box  

NS4-100, NS4-100W 

HB-55  HD-3 or HD-5  150mA

limit externally

 @15.0 - 33.0V max 

 

3” Octagonal 

NS6-100, NS6-100W 

HB-55  HD-3 or HD-5  150mA

limit externally

 @15.0 - 33.0V max 

4” Octagonal / 4” Square 

NS4-220, NS4-220W 

HB-3 

HD-3 or HD-5  93mA (136mA @33.0V max) 

3” Octagonal 

NS6-220, NS6-220W 

HB-3 

HD-3 or HD-5  93mA (136mA @33.0V max) 

4” Octagonal / 4” Square 

NS4-221, NS4-221W 

HB-4 

HD-3 or HD-5  46mA (77mA @33.0V max) 

3” Octagonal 

NS6-221, NS6-221W 

HB-4 

HD-3 or HD-5  46mA (77mA @33.0V max) 

4” Octagonal / 4” Square 

NS4-224, NS4-224W 

HB-5 

HD-3 or HD-5  43mA (58mA @30.0V max) 

3” Octagonal 

NS6-224, NS6-224W 

HB-5 

HD-3 or HD-5  43mA (58mA @30.0V max) 

4” Octagonal / 4” Square 

HSC-220R, HSC-220RW 

2 Wire Relay Base

 

HB-72  HD-3 or HD-5  88mA (98mA @ 26.5V max) 

4” Octagonal / 4” Square 

HSC-221R, HSC-221RW 

2 Wire Relay Base

 

HB-71  HD-3 or HD-5  49mA (62mA @ 30.0V max) 

4” Octagonal / 4” Square 

HSC-224R, HSC-224RW 

2 Wire Relay Base

 

HB-73  HD-3 or HD-5  43mA (58mA @ 30.0V max) 

4” Octagonal / 4” Square 

HSC-4R 

4 Wire 24V Base 

N/A 

HD-3 or HD-5  43mA (58mA @ 30.0V max) 

4” Octagonal / 4” Square 

HSC-4R12 

4 Wire 12V Base

 

N/A 

HD-3 or HD-5  47mA (75mA @ 18.0V max) 

4” Octagonal / 4” Square 

NOTES: 
Alarm current for 2-wire operation applies to the FACP Initiating Device Circuit and detector. 
Alarm current for 4-wire operation applies to the Auxilliary Power Supply and detector. 
NS4-100 and NS6-100 must be current limited by the FACP  
Standard base is ivory color, W suffix indicates white color 

 
Refer to the Technical Bulletin HA-06-434 issued 07/21 (accessible at www.Hochiki.com) for the following UL listed 
compatible detectors. Connect these detectors only to a listed-compatible control panel. Refer to the control panel 
installation manual for additional instructions. Smoke detectors are not to be used with detector guards unless the 
combination has been evaluated and found suitable for that purpose: 

SOC-24V/SOC-24VN/SOC-24VW Smoke Detector (Compatibility ID HD3) 
SOE-24V/SOE-24V (WHT) Multi-criteria Smoke Detector (Compatibility ID HD3) 
SOE-24H/SOE-24H (WHT) Multi-criteria Smoke and Heat Detector (Compatibility ID HD3) 
DCD-135/DCD-135W Fixed Temperature and Rate of Rise Detector (Compatibility ID HD3) 
DCD-190/DCD-190W Fixed Temperature and Rate of Rise Detector (Compatibility ID HD3) 
DSC-EA/DSC-EAW Rate of Rise Dry Contact Heat Detector 
DFE-135/DFE-135W/DFE-135C Fixed Temperature Dry Contact Heat Detector 
DFE-190/DFE-190W/DFE-190C Fixed Temperature Dry Contact Heat Detector 
 

Detectors must be installed and maintained in accordance with applicable NFPA standards, local codes and any authority 
having jurisdiction.  Refer to NFPA 72 "National Fire Alarm and Signaling Code" for installation guidelines and testing 
procedures. Smoke detectors should be tested in accordance with NFPA 72, section on "Inspection, Testing and 
Maintenance".  

Seal conduit openings in the electrical box with 3M Weatherban #606 nonflammable sealing compound (or equivalent) 
to reduce the stack effect. Attach the detector to the base by turning the detector clockwise until it stops. 

 