Section V.
Parameter Function Table
Fig. 5-5 VF separation schematic diagram
5.6
Input terminal
:
P4.00-P4.40
HV590 series inverter has 6 multifunctional digital input terminals (DI1 to DI6), of which DI5
can be used as high-speed pulse input terminal, and HV590 series inverter also has 2 analog
input terminals.If system needs more input/output terminal, it can be equipped with multi-
function input/output expansion card and 1 analog input terminal(AI3x).
Multi-function
input/output
expansion
card
has
4
multi-function
digit
input
terminal(DI7~DI10).
Code
Description/Display
Setting Range
Factory
Setting
Change
Limite
P4.00 DI1terminal function selection
0~59
1
★
P4.01 DI2 terminal function selection
0~59
4
★
P4.02 DI3 terminal function selection
0~59
9
★
P4.03 DI4 terminal function selection
0~59
12
★
P4.04 DI5 terminal function selection
0~59
13
★
P4.05 DI6 terminal function selection
0~59
2
★
P4.06 DI7 terminal function selection
0~59
12
★
P4.07 DI8 terminal function selection
0~59
13
★
P4.08 DI9 terminal function selection
0~59
14
★
P4.09 DI10 terminal function selection 0~59
15
★
These parameters are used to set digital multi-function input terminals, as shown in the table below
:
Setting
Function
Specification explanation
0
No- function
Set useless terminals to “no function”, in order to prevent
misoperation.
1
Forward command (FWD)
The forward jog and reverse jog of the inverter are
controlled via the external terminals.
2
Reverse command (REV)
Actual voltage fall time
Output voltage V
Setting voltage fall time
t
Rated motor voltage
Output voltage target value
Actual voltage rise time
Setting voltage rise time