HMS Intesis INKNXMBM1000100 Installation Sheet Download Page 1

  

 

 

 

 

 
 

© HMS Industrial Networks S.L.U - All rights reserved                

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

    Rev.1.0 

                1 / 2

 

 

INKNXMBM1000100 

Modbus RTU Master to KNX gateway

 

Order Code:

 INKNXMBM1000100 

Installation Sheet rev.1.0 

HMS Industrial Networks S.L.U ©

 

 

 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

SAFETY INSTRUCTIONS 

     

!

     

WARNING 

Follow  carefully  this  safety  and  installation  instructions. 
Improper work may lead to serious harmful for your health 
and also may damage seriously the Intesis gateway and/or 
any other equipment connected to it. 

 

The  Intesis  gateway  must  be  installed  by  accredited  electrician  or 
similar  technical  personnel,  following  all  the  safety  instructions  given 
here  and  in  accordance  always  with  the  country  legislation  for 
installation of electric equipment. 

 

The Intesis gateway cannot be installed outdoors or exposed to direct 
solar radiation, water, high relative humidity or dust. 

 

The  Intesis  gateway  must  only  be  installed  in  a  restricted  access 
location.  

 

In  case  of  wall  mount,  fix  firmly  the  Intesis  device  on  a  not  vibrating 
surface following the instructions next. 

 

Disconnect  always  power  of  any  wires  before  manipulating  and 
connecting them to the Intesis gateway. 

 

Respect  always  the  expected  polarity  of  power  and  communication 
cables when connecting them to the Intesis device  

 

Supply  always  a  correct  voltage  to  power  the  Intesis,  see  details  of 
voltage  range  admitted  by  the  device  in  the  technical  characteristics 
below.  

 

CAUTION:  The  device  is  to  be  connected  only  to  networks  without 
routing to the outside plant, all communication ports are considered for 
indoor only and can be connected SELV circuits only. 

 

This  device  was  designed  for  installation  in  an  enclosure.  To  avoid 
electrostatic  discharge  to  the  unit  in  environments  with  static  levels 
above 4 kV, precautions should be taken when the device is mounted 
outside  an  enclosure.  When  working  in  an  enclosure  (ex.  making 
adjustments,  setting  switches  etc.)  typical  anti-static  precautions 
should be observed before touching the unit. 

 

Safety instructions in other languages can be found at: 

https://intesis.com/docs/manuals/v6-safety 

 

INSTALLATION 

Follow instructions next to properly install the gateway. 

 
Mount the Intesis device on the wall or inside a close electrical junction 
box (respect the safety instructions given in this document). 
 
Disconnect the KNX power supply from the KNX bus. 

 

Connect the communication cables to the Intesis device, see details on 
CONNECTIONS below. 
 
Reconnect the KNX power supply to the KNX bus. 
 
Connect EIA485 device(s) to its power supply. 

 

NOTE: 

The device cannot be installed in air-handling space.

 

 

CONNECTIONS 

Owner’s Record 

The serial number is located at the rear of the gateway. 
Record  this  information  in  the  space  provided  below. 
Refer  to  it  whenever  you  contact  upon  your  gateway 
dealer or support team regarding this product. 

Serial No.

                         

KNX Port 
Connect the KNX TP1 bus to conn and - of gateway

’s KNX port. 

Respect the polarity and use a KNX standard cable. 

 

 

Port A / Modbus RTU 
Connect the EIA485 bus to connectors A2 (A-), A3 (B+) and A1 (SNGD) 
of  gateway

’s  Port  A.  Remember  the  characteristics  of  the  standard 

EIA485 bus: maximum distance of 1200 meters, maximum 32 devices 
connected to the bus, bus polarization and in each end of the bus it must 
be a termination resistor of 120 Ω. 

 

CONFIGURATION 

 

 

IMPORTANT

:

 

If  the  INKNXMBM1000100  gateway  is  not  placed  at  one  end  of  the  Modbus 

channel,  the  terminal 

resistor should be deactivated. Remove Jumper 1 to deactivate the 120 Ω 

terminal resistor.

  

The bus should be polarized only in one location on the line. The INKNXMBM1000100 incorporates 
2 jumpers to introduce polarization to the line. It is recommended to keep polarization in the master 
only. If other device is polarized, remove jumpers 2 and 3 to deactivate polarization in the gateway. 

 

 

 

Use the 

ETS

 to configure the gateway. 

 

Follow  the  instructions  on  the  user’s  manual  for  configuring  and 
commissioning the interface. See below how to obtain the user’s manual 
and ETS database. 

 

https://www.intesis.com/products/protocol-translator/knx-
gateways/modbus-rtu-master-to-knx 

 

 