7. PLC Configuration
7.1. Export Product EDS File
Option for Ethernet/IP Adapter.
Option if the PLC program requires a product file, EDS (Electronic Data Sheet) file to configure the EtherNet/IP
PLC to use the Communicator.
Figure 34. Export Product EDS File
You find the
EtherNet/IP™ EDS
file on the Communicator built-in web interface EtherNet/IP™ page, Files &
firmware page and on the Support page.
To export the EDS file:
1. Click EDS file.
The EDS file is downloaded to your PC.
7.2. Addressing and Register Mapping
7.2.1. Data From Modbus TCP Network to Serial-Subnet
Process data offset
Coil address
Holding register
0x0000 — 0x001
0x0000 — 0x000F
0x0000
0x0002 — 0x0003
0x0010 — 0x001F
0x0001
...
...
...
0x05D8 — 0x05D9
0x2EC0 — 0x2ECF
0x02EC
0x05DA — 0x05DB
0x2ED0 — 0x2EDF
0x02ED
7.2.2. Data From Serial-Subnet to Modbus TCP Network
Process data offset
Discrete input address
Input register
Holding register
0x0000 — 0x001
0x0000 — 0x000F
0x0000
0x0800
0x0002 — 0x0003
0x0010 — 0x001F
0x0001
0x0801
...
...
...
...
0x05D8 — 0x05D9
0x2EC0 — 0x2ECF
0x02EC
0x0AEC
0x05DA — 0x05DB
0x2ED0 — 0x2EDF
0x02ED
0x0AED
PLC Configuration
Anybus
®
Communicator
™
- EtherNet/IP
™
Adapter to Modbus TCP Server
SCM-1202-196 Version 1.0
Page 37 of 56