Appendix A
A. Technical Specification
A.1 Protective Earth (PE) Requirements
The product must be connected to protective earth (PE) via the DIN-rail connector in order to achieve
proper EMC behavior.
HMS Industrial Networks does not guarantee proper EMC behavior unless these PE requirements are
fulfilled.
Note
: The shield of the RJ45 connector is not connected directly to PE. As all nodes in a PROFINET
network have to share chassis ground connection, the PROFINET cable shield has to be connected to
the chassis ground at each node in the network. For further information, see “PROFINET Installation
Guideline for Cabling and Assembly”, order no. 8.072, available for download at www.PROF-
INET.com.
A.2 Power Supply
Supply Voltage
The gateway requires a regulated 24 V ±10 % DC power source.
Power Consumption
Typical: 100 mA at 24 V.
Maximum: 150 mA at 24 V
A.3 Environmental Specification
A.3.1 Temperature
Operating
-25
º
to +55
º
Celsius
(Test performed according to IEC-60068-2-1 and IEC 60068-2-2.)
Non Operating
-40
º
to +85
º
Celsius
(Test performed according to IEC-60068-2-1 and IEC 60068-2-2.)
A.3.2 Relative Humidity
The product is designed for a relative humidity of 5 to 95% non condensing.
Test performed according to IEC 60068-2-30.