Intesis
TM
BACnet Server
– PROFINET
User Manual r1.0 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
8 / 46
2.
Protocol Implementation Conformance Statement
BACnet Protocol Implementation Conformance Statement (PICS)
Date: 2018-05-16
Vendor Name: HMS Industrial Networks S.L.U
Product Name: INBACPRT---0000
Product Model Number: INBACPRT---0000
Application Software Version: 1.0.0.0
Firmware Revision: 14.0.1.0
BACnet Protocol Revision: 14
Product Description:
BACnet MS/TP & IP Server
– PROFINET Gateway
Abstraction of PROFINET data as BACnet Objects.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
Additional BACnet Interoperability Building Blocks Supported (Annex K):
Reference of BIBBs List
Segmentation Capability:
Segmented request supported
No
Yes Window Size
· 16 ·
Segmented responses supported
No
Yes Window Size
· 16 ·
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200
MS/TP slave (Clause 9), baud rate(s):
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium: _____
Other: