52 (124)
7.7.3
Configure Frame Field Settings
Procedure
1.
In the Transaction templates list, select a transaction template to configure.
2.
In the Transaction template settings select a
Field
to configure.
→
The Field sidebar opens, on the right side of the screen.
3.
Configure the Field settings.
Limit can only be added as a Response frame field.
Node address
Frame field representing the Node address of the node. A constant byte that holds a copy of the
nodes address when the transaction is used by a node.
When the transaction template is used by a node, the Node address field will automatically be
replaced with the actual node address of the node.
Constant
•
Name:
You can name the Frame Field to make it easier to identify.
•
Type:
Specify the number of bytes in the frame. Select Byte (1 byte) (Default), Word (2
bytes), Double word (4 bytes), Array of bytes or String.
•
Endianess:
Select Big-endian (Default) or Little-endian.
•
Fixed field*:
Select Yes, set here (Default) or No, set when used.
•
Length:
Valid for Array of bytes. Enter a byte offset value between 0 and 32 byte. Default
value is 1 byte. Enter a Value for each Byte (0–31).
•
Value:
The value of the Constant in the frame. Enter a value between 0 (Default) and 255.
•
Min value:
Specify the minimum value that can be set when the template is used.
•
Max value:
Specify the maximum value that can be set when the template is used.
•
Default value:
Default value set when the template is used.
Anybus
®
Communicator
™
User Manual
SCM-1202-162 1.1 en-US