background image

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

INSTALLATION

INSTRUCTIONS

HUMIDITY TRANSMITTERS

RHT Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank you for choosing an HK Instruments RHT series relative hu

-

midity transmitter. The RHT series is intended for use in commercial 
environments in HVAC/R applications.

The RHT series measures relative humidity (rH) and temperature (T). 
Each measurement parameter (rH, T) has a separate field configur

-

able output.

The  RHT  series  relative  humidity  transmitters  are  available  with 
Modbus configuration, relay and touchscreen display.

RHT series devices are commonly used to monitor:
•  humidity and temperature levels in offices, public spaces, hospitals, 

meeting rooms and classrooms

•  humidity and temperature in various commercial applications
•  humidity and temperature in HVAC/R environment

SPECIFICATIONS

Performance

Measurement ranges:

Temperature: 0...50 °C

Relative humidity: 0–100 %

Accuracy:

Temperature: <0.5 ºC

Relative humidity:  

±2...3 % at 0...50 °C and 10–90 % rH

Total error band includes accuracy, hysteresis and

temperature effect over 5...50 °C and 10–90% rH.

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

°C and % rH

Measuring element:

Temperature: Pt1000

Relative humidity: 

Thermoset polymer capacitive sensing element

Environment:

Operating temperature: 0...50 °C

Storage temperature: -20...70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 99 x 90 x 32 mm

Weight: 

150 g

Mounting: 

3 screw holes slotted, 3.8 mm

Materials: 

Case: ABS

Protection standard: 

IP20

Display (Optional)

Touchscreen

Size: 77.4 x 52.4 mm

Electrical connections:

Power supply:  

 

5-screw terminal block

 

(24 V, GND, rH, T, NC)

 

0.2–1.5 mm

2

  (12–24 AWG)

Relay out:  

 

3-screw terminal block

 

(NC, COM, NO)

 

0.2–1.5 mm

2

  (12–24 AWG)

Electrical

Input:  

 

24 VAC or VDC, ±10 %

 

Current consumption: max 90 mA (at 24 V) +  

 

10 mA for each voltage output or 20 mA for  

 

each current output

Temperature output signal:  

 

0–10 V, R>1 kΩ

 

2–10V, R>1 kΩ

 

4–20 mA, R<500 Ω

Relative humidity output signal:  

 

0–10 V, R>1 kΩ

 

2–10 V, R>1 kΩ

 

4–20 mA, R<500 Ω

Relay out:  

 

SPDT Relay, 250 VAC / 30 VDC / 6 A

 

Adjustable switching point and hysteresis

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

LVD Directive 2014/35/EU

WEEE Directive 2012/19/EU

INTRODUCTION

WARNING

APPLICATIONS

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Summary of Contents for RHT Series

Page 1: ...temperature levels in offices public spaces hospitals meeting rooms and classrooms humidity and temperature in various commercial applications humidity and temperature in HVAC R environment SPECIFICATIONS Performance Measurement ranges Temperature 0 50 C Relative humidity 0 100 Accuracy Temperature 0 5 ºC Relative humidity 2 3 at 0 50 C and 10 90 rH Total error band includes accuracy hysteresis an...

Page 2: ...l Locate the unit in an area with good ventilation and an average temperature where it will be responsive to changes to the room conditions The RHT may be mounted on a flat surface Do not locate the RHT where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a...

Page 3: ...ck plate or for surface wiring select a knockout on the top or bottom of the wall plate as shown in Figure 2a 2 Connect the wires as shown in Figure 2b and 2c STEP 3 CONFIGURATION WIRING DIAGRAMS CONTINUED Configuration of the RHT series device consists of 1 Configuring the jumpers see step 4 2 Configuration menu options Display versions only See the user manual for further details Figure 2a Routi...

Page 4: ...t done by the seller or his her authorized representative The selection of materials for devices prone to corrosion is the buyer s responsibility unless otherwise is legally agreed upon Should the man ufacturer alter the structure of the device the seller is not obligated to make comparable changes to devices already purchased Appealing for warranty requires that the buyer has correctly fulfilled ...

Reviews: