background image

Installation version 6.0 2018

INSTALLATION

INSTRUCTIONS

AIR FLOW AND VELOCITY TRANSMITTERS

AVT Series

Thank you for choosing an HK Instruments AVT series air velocity 

transmitter. The AVT series is intended for use in commercial environ

-

ments.  It  is  designed  with  a  duct  mount  probe  and  adjustable  collar 
suitable for round or rectangular ducts. The AVT series provides sepa

-

rate readings for air velocity and temperature.

The AVT series comes with three measurement ranges in a single de

-

vice (0–2 m/s, 0–10 m/s, 0–20 m/s). The AVT series is available with 
optional display and relay.

• READ THESE INSTRUCTIONS CAREFULLY BEFORE

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS

DEVICE.

• Failure to observe safety information and comply with

instructions can result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.

• To avoid electrical shock or damage to equipment, disconnect

power before installing or servicing and use only wiring with
insulation rated for full device operating voltage.

• To avoid potential fire and/or explosion do not use in potentially

flammable or explosive atmospheres.

• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered

system whose specifications and performance characteristics
are not designed or controlled by HK Instruments. Review
applications and national and local codes to assure that the
installation will be functional and safe. Use only experienced and
knowledgeable technicians to install this device.

Performance

Measurement ranges:

Velocity:  

Range: 0–2 m/s

Range: 0–10 m/s

Range: 0–20 m/s

Temperature: 0−50 °C 

Accuracy:

Velocity:  

Range: 0...2 m/s: <0.2 m/s + 5 % from reading

Range: 0...10 m/s: <0.5 m/s + 5 % from reading

Range: 0...20 m/s: <1.0 m/s + 5 % from reading

Thermal shift: ±0.8 % FS / °C

Units calibrated at 22 °C. Rapid thermal shift 

stabilisation time 10 min. 

Temperature: <0.5 ºC (velocity > 0.5 m/s)

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

m/s and °C

Measuring element:

Temperature: ntc10k

Velocity: Pt1000

Environment:

Operating temperature: 0...50 °C

Storage temperature: -20...70 °C

Humidity: 0 to 95 % rH, non-condensing

Physical

Dimensions: 

Case : 90.0 x 95.0 x 36.0 mm

Probe: OD 10 mm, length 210 mm from bottom of the 

cover

Immersion Length with Flange: Adjustable 50–180 mm

Weight: 

220 g

Mounting: 

Mounting flange, ø 4.0 mm

Materials:  

Case: ABS

Lid: PC

Probe: Stainless steel 304

Mounting flange: LLPDP

Protection standard: 

IP54

Display

3 1/2 digit LCD backlit display

Size: 45.7 x 12.7 mm

Electrical connections:

Power supply & signal out: 4-screw terminal block

12–24 AWG (0.2–1.5 mm

2

)

Relay Out: 3-screw terminal block

12-24 AWG (0.2–1.5 mm

2

)

Cable entry: 

M16

Electrical

Input: 24 VDC / 24 VAC ± 10 %

Current consumption 35 mA (50 mA with relay)  

+ 40 mA with mA-outs

Output signal 1: (T out)

0–10 V (linear to temperature)

L min 1 kΩ

4–20 mA (linear to temperature)

L max 400 Ω

Output signal 2: (v out)

0–10 V (linear to m/s)

L min 1 kΩ

4–20 mA (linear to m/s)

L max 400 Ω

Relay Out: 3-screw terminal block

(NC, COM, NO)

Potential free SPDT

250 VAC, 6A / 30 VDC, 6 A adjustable switching point

and hysteresis

Conformance

Meets the requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

LVD Directive 2014/35/EU

WEEE Directive 2012/19/EU

SPECIFICATIONS

INTRODUCTION

AVT series devices are commonly used in HVAC/R systems for:
• in-duct air flow and velocity monitoring
• in-duct temperature monitoring
• VAV applications

APPLICATIONS

WARNING

RoHS 2

2011/65/EU

Summary of Contents for AVT Series

Page 1: ... 2 m s 0 2 m s 5 from reading Range 0 10 m s 0 5 m s 5 from reading Range 0 20 m s 1 0 m s 5 from reading Thermal shift 0 8 FS C Units calibrated at 22 C Rapid thermal shift stabilisation time 10 min Temperature 0 5 ºC velocity 0 5 m s Technical Specifications Media compatibility Dry air or non aggressive gases Measuring units m s and C Measuring element Temperature ntc10k Velocity Pt1000 Environm...

Page 2: ... m s C 36 0 95 210 0 15 0 15 0 70 Push button Terminal block Jumpers Terminal block for relay Air flow direction Air flow direction Air flow direction Air flow direction Air flow direction Strain relief facing down Figure 1c Mounting orientation Tighten the screw INSTALLATION 1 Select the mounting location on a duct 2 Use the mounting flange of the device as a template and mark the screw holes 3 Mount ...

Page 3: ...GE CONTINUED Tout vout 24 V GND Power supply 24 VDC 24 VAC V A V A Output 0 10 V 4 20 mA temperature Output 0 10 V 4 20 mA velocity r d No jumper Circuit open Jumper stored Jumper installed Cicuit closed Grey colour indicates that a jumper is installed Figure 3b Jumper installation J1 Jumper J1 Installed J2 Jumper J2 Not installed Range 2 0 2 m s J1 Jumper J1 Not installed J2 Jumper J2 Installed R...

Page 4: ...less product and sending it to the buyer Delivery costs for the repair under warranty will be paid by the buyer and the return costs by the seller The warranty does not comprise damages caused by accident lightning flood or other natural phenomenon nor mal wear and tear improper or careless handling abnormal use over loading improper storage incorrect care or reconstruction or changes and installa...