INSTRUCTION MANUAL 

VIBRATION TYPE LEVEL SWITCH 

HTM-20N Series 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Doc. no. : HTM20N_IM_Eng_Rev.3.2 

Issue date: 2020. 09 

Summary of Contents for HTM-20N Series

Page 1: ...ICE FACTORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 82 31 950 9700 FAX 82 31 943 5600 www hitrol com INSTRUCTION MANUAL VIBRATION TYPE LEVEL SWITCH HTM 20N Series Doc no HTM20N_IM_Eng_Rev 3 2 Issue date 2020 09 ...

Page 2: ...ther proof Version PBT 5 Weather proof Version AL C 6 Attachment and Precautions 7 Installation on Side Horizontal 7 Installation on Top Vertical 7 Technical Data 8 Use 9 Maintenance 9 Failure Check 9 Precautions for Removal 9 Precautions for Installation 10 Precautions for Transportation and Assembly 10 Precautions for Lead In Method of External Wiring Ex proof 10 Precautions for Grounding Ex pro...

Page 3: ...the contact output Level of different powder types can be detected It can measure powder particles ranging from small to large The membrane is made of stainless steel with a solid structure and a high bearing capacity The wiring is simple It is customizing with the key button It has a simple structure for easy maintenance It has Ex proof and Dust proof structures HPV Series The HTM 20N Series is a...

Page 4: ...ion Side Side Top Top Contact Rating AC 250V 5A DC 30V 5A Item Specification Module M 20N Microprocessor 16Bit Microprocessor Power Consumption AC Stand by AC110 4 8W AC220V 9W Active AC110 5 6W AC220V 9 8W DC Stand by DC 24V 1 5W Active DC 24V 2 3W Oscillation Frequency 85Hz 5Hz Sensitivity Resolution 0 1V Function Adjustment Sensitivity Relay Delay Relay Return Time Relay Contact Control Normal ...

Page 5: ...HTM 20N Series HITROL CO LTD 5 Dimensions Weather proof Version PBT HTM 20N A HTM 20N B HTM 20N C Screw Type Flange Type HTM 20N B HTM 20N C ...

Page 6: ...HTM 20N Series HITROL CO LTD 6 Weather proof Version AL C HTM 20NH A HTM 20NH B HTM 20N C Screw Type Flange Type HTM 20NH B HTM 20N C ...

Page 7: ... the tuning fork Refer to Fig 1 Sensor shall be installed at the place far from inlet of the tank and protector shall be installed in order to protect the sensor from damage by falling medium if it is installed at the inlet Refer to Fig 1 Cable lead in inlet shall be installed facing the ground as shown in the figure Refer to Fig 1 Sun cover shall be installed to protect the housing from the damag...

Page 8: ...Process Pressure Up to 10kg 150 HTM 20N A HTM 20N B 최대 Up to 2kg HTM 20N C Relative Humidity Good for 0 100 Ratio between the vapors in the air and that required for saturation at the same temperature Ambient Temp Housing 20 60 HTM 20N Series Process Temperature MAX 80 HTM 20N A HTM 20N B 공정온도 Process temperat ure MAX 120 HTM 20NH A HTM 20NH B 공정온도 Process temperature MAX 60 HTM 20N C ⓐ ⓑ ⓐ ⓒ T am...

Page 9: ... so they shall be removed regularly Remove any sticky object from the device when cleaning the tank or silo If the medium moves fast or the agitator works in the tank perform regular inspection to prevent mechanical damage to the sensor It may cause sensor error and malfunction so conduct a regular water proof check When measuring sticky material check if such material grows Remove them regularly ...

Page 10: ...l Grounding is connected and shipped by the manufacturer External Grounding 4 4mmSQ Outside of Head PBT Outside of Head AL C Connect the flanges or bolts with the same specifications Make sure to insert washers between bolts and nuts to prevent loosening Make sure to insert gaskets between flanges Select the gaskets in consideration of the temperature of the content and the pressure inside the con...

Page 11: ...ct Precautions for Use Make sure to connect the product and vessel using required tools for sure Keep the lock key safe and make sure that it is locked Do not apply high impact to the product Precautions for Wiring Make sure to wire contacts correctly Internal ground inside product housing and external ground shall be connected Wire and supply the power to the product after checking the specificat...

Page 12: ...amage found under normal operating conditions If it is not about the failure of product the service charge will be payable You can request A S at our website or by contacting our headquarters Headquarters Factory Laboratory Contact Number ADRESS HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea T E L 031 950 9700 Headquarters A S F A X 031 943 5600 Headquarters A S ...

Page 13: ...HTM 20N Setting Guide Tuning Fork Type Vibration Level Switch Doc no Rev0 0 Issued Date 2020 08 31 APPENDIX O ...

Page 14: ...nt 0 1s 3 RT Relay Return Time Adjustment Time Range 0 5s 1s 10s Adjustment 0 1s 4 Fail Safe Mode Relay Transformation Adjustment N C N O 5 DET Measurement Status LED OFF Red 6 RLY Relay Status LED N C OFF Green N O Green OFF 7 PWR Power Status Display 8 UART M 20N Status Display Communication Port 9 Power Power AC DC 10 Relay Out Relay Contact Out DPDT ...

Page 15: ...ng 1 The reference setting method according to the Initialization Setting Method No Function Method 1 Vibration Frequency Tuning The SEN VR status is the most sensitive according to the Initialization Setting Method Keep this status for sensitive use Initialization Setting Status Relay Delay Time 0 5s Relay Return Time 0 5s SEN 0 Fail Safe Mode NC ...

Page 16: ... the SEN VR to the right until the DET LED turns off to set the reference value No Function Method 1 Tuning Setting Status The SEN VR status is the most sensitive state according to the Tuning Setting Method Keep this status for sensitive use 2 Sensitivity Adjustment You can adjust the sensitivity by adjusting the SEN VR Sensitivity Adjustment Method Before Adjusting SEN VR After Adjusting SEN VR ...

Page 17: ...ment You can adjust the relay operation time after not detecting the measurement No Function Method 1 DT Relay Delay Time Time Adjustmnet Range 0 5s 1s 10s Adjustment 0 1s No Function Method 1 RT Relay Return Time Time Adjustment Range 0 5s 1s 10s Adjustment 0 1s Relay Delay Time Relay Return Time ...

Page 18: ...tact status to Relay Contact N O No Function Method 1 N C Relay Contact Out Default Status After detecting the measurement the contact point changes from N C N O LED Status No Function Method 1 N O Relay Contact Out Opposite Status After detecting the measurement the contact point changes from N O N C LED Status ...

Page 19: ...ensitivity setting value relay setting etc Monitoring Method Using PC Component PC USB Cable typical USB to Micro USB B UART Adaptor M 20N PC UART RUN SCREEN M 20N PC UART Component USB Cable Min Frequency Setting Value for Medium Detection Max Frequency Setting Value for Medium Non detection Current Measurement Voltage Sensitivity Setting State Voltage Threshold Relay Delay Time Adjustments Relay...

Page 20: ...p Refer to Serial USB Terminal Install Guide M 20N Smartphone UART Component USB Cable M 20N Smartphone UART Execution Enter Password Open App Home Screen Select UART Connection M 20N Smartphone UART Exit Select UART Disconnection Exit Program Enter exit command Enter exit and Fly command Run Screen Enter PW and Fly command ...

Page 21: ...Doc no Rev0 0 Issued Date 2020 04 29 Serial USB Terminal Serial USB Terminal Install Setting Guide Application Level Switch Level Transmitter APPENDIX H ...

Page 22: ...SB Terminal App Search and Install a App that Serial USB terminal in the App Store Serial USB Terminal Setting Run The Serial USB Terminal Icon Four types of environments must be set up for normal operation of Serial USB Terminal Serial Terminal Receive Send ...

Page 23: ...rminal Show connection message Show timestamps Setting Show connection message ON OFF Show timestamps ON OFF The size of the Terminal Font is the size set in the Smartphone Terminal Setting Terminal Font Setting Default Complete Default Complete Default Setting Complete Select Baud rate ...

Page 24: ... no Rev0 0 Issued Date 2020 04 29 Receive Newline Setting Newline CR LF Carriage Return Line Feed Check Send Newline Setting Newline Auto same as Receive CR Select Newline Default Setting Complete Default ...

Page 25: ...al echo Clear input on send Setting Local echo ON OFF Clear input on send OFF ON Local echo Setting Clear input on send Setting For detailed instructions refer to the manual of each product Select Clear input on send Select Local echo Complete Complete Select Character delay Complete Setting Default ...