HCC(HPC)-96RF-R Series 

 

 

        HITROL CO., LTD.                                                                                8 

 

■ Connection of HCC-96RF-R(Sensor) and HLC-96RF-R(Controller) 

- Prepare the cable (CVVS 3C) that connects the sensor and combination unit and connect as 

shown below. (The distance between HCC-96RF-R and HLC-96RF-R is available up to 500m.) 

 

 
 
 
 
 
 

 
 

 

■ Power Connection 

-  The  power  specification  of  the  instrument  consists  of  AC  110V  or  220V,  which 

energizes the sensor power supply. 

- Be sure to check the following items before wiring: 

Is the specified power voltage used? 
Has the CCVS wires been used for the wires between the controller and the amplifier? 
Are separate conduits other than power lines used when the controller and amplifier are engaged? 

 
■ Output Connection 

- The contact capacity of relay is AC 250V, 5A / DC 30V, 5A, and larger capacity values 

require connecting external relay. 

 

 
 
 
 
 

■ Initial / General Adjustment 

1. Set the 

Fine

 variable resistor to 0%. 

2. Turn the 

Coarse

 variable resistor clockwise 18 times. 

3. Slowly rotate the

 Coarse

 variable resistor clockwise until the detect LED changes from 

yellow to red. 

4. Rotate clockwise or counter-clockwise, repeat the detect LED to operate from red to 

yellow or from yellow to red 3 times, then set it at the point where the yellow light is on. 

5.  Moving  the 

Fine

  variable  resistor  from  0%  to  10%  indicates  setting  at  ultra-high 

sensitivity (∠c 1pF). 

6. From now on, turn the 

Fine

 variable resistor to set according to the dielectric ratio of 

the measuring instrument. 

 

Wiring 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Settings 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

Summary of Contents for HCC-96RF-R Series

Page 1: ...e date 2021 01 HITROL CO LTD HEAD OFFICE FACTORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 943 5600 www hitrol com INSTRUCTION MANUAL RADIO FREQUENCY TYPE LEVEL SWITCH HCC 96RF R Series HPC 96RF R Series ...

Page 2: ...ble of Contents Overview 3 Characteristic 3 Operating Principle and Composition 3 Specification 4 Sensor 4 Combination Unit 4 Dimensions 5 Sensor 5 Combination Unit 6 Installation 7 Precautions for Installation 7 Wiring 8 Settings 8 Failure Check 9 Maintenance 10 Precautions for Removal 10 Precautions for Inserted External Wire Ex proof 10 Precautions for Grounding Ex proof 10 Safety and Environme...

Page 3: ...ittivity and conductance value that are different from air the impedance of the signal circuit is changed when medium touches the probe This change causes a shift in phase of the RF signal A phase difference between the active signal and reference signal causes the output circuitry to operate This type can only be applied to solid dust For cylindrical tanks the capacitance can be obtained as shown...

Page 4: ... Safe Low High Select of Dip Switch Process Connection 50A JIS 10K Material Housing AL C Wetted part SUS 316L PPS SUS 316L CERAMIC SUS 316L PPS Cable Entry PF 3 4 F Adaptor PF 1 2 NPT 3 4 Combination Unit HLC 96RF R or HLC 96RF RACK Combination Unit Model HLC 96RF R HLC 96RF RACK Installation Local Type Rack Type Power Source AC 110V or 220V AC 90V 240V Contact Form DPDT Contact Rating AC 250V 5A ...

Page 5: ...HCC HPC 96RF R Series HITROL CO LTD 5 Sensor Some tolerances may occur with actual products Dimensions The dimensions on the following pages are indicated in mm HCC 96RF R HCC 96RF RH HPC 96RF R ...

Page 6: ...when there are 10ea of Control Card HLC 96RF RA The Control Card HLC 96RF RA can be used up to 12ea Some tolerances may occur with actual products HLC 96RF R LOCAL TYPE Control Card Test Card Power Card HLC 96RF RACK RACK TYPE CONTROL CARD HLC 96RF RA TEST CARD POWER CARD HD 44 ...

Page 7: ...he instrument causing unstable operation For side mounting installations an inactive rod shall be exposed to the inside of the tank by at least 50mm and it is recommended that the probe be tilted by 15 degrees to the horizontal surface A foreign object may cause malfunction between the nozzle and the probe Probe shall be installed to avoid the inlet side of the measuring instrument and the protect...

Page 8: ...sed when the controller and amplifier are engaged Output Connection The contact capacity of relay is AC 250V 5A DC 30V 5A and larger capacity values require connecting external relay Initial General Adjustment 1 Set the Fine variable resistor to 0 2 Turn the Coarse variable resistor clockwise 18 times 3 Slowly rotate the Coarse variable resistor clockwise until the detect LED changes from yellow t...

Page 9: ...l switch circuit The measurement cannot detected Sensitivity setting is wrong Readjust in accordance with sensitivity adjustment sequence The measurement has high conductivity Use a concealed sensing part The detector was corroded Corrosion occurs due to chemical action Use a concealed sensing part to prevent corrosion The detector eroded or worn out Sensor is physically damaged because of the hig...

Page 10: ...ed while opening or closing the cover of product Unlock the lock key before removing the cover Ex proof Disassemble work shall be done with the power off External ground is located on top of cable entry and the grounding wire to connect external ground shall be 4 4mmSQ Internal ground is connected before shipment The internal grounding wire shall be the same size as the power line and the size of ...

Page 11: ...pact to the product Precautions for Wiring Make sure to connect contacts with the correct terminals Refer to Wiring Wire and supply the power to the device after checking the specifications Pay attention to prevent electric shock Disposal of Product Make sure to separate the amplifier and main unit from housing before disposing the products No part ex Mercury switch has influence on the environmen...

Page 12: ...F A X 031 943 5600 Headquarters A S Understand the aforementioned and do not exceed 240 and 500 respectively for the liquid in the general and high temperature vessels to use the product In addition make sure that the ambient temperature of housing is kept at 20 60 An Ex proof product is a pressure resistant and Ex proof type so never open the cover during operation Ex proof products are designed ...