39
English
EWFAIB
20
2
5
3
0
Power supply
V/ph/Hz
400 ± ( 10%)/3+N/50
Maximum power input
kW
12.0
14.3
14.3
Maximum current input
A
24.9
30.1
30.1
Start-up corrent
A
5.2
5.2
5.2
External fuses
A
32
32
32
Max cable section
(*)
mm
2
10
10
10
HEAT EXCHANGER RESISTANCE
Power supply
V/ph/Hz
230 ± ( 10%)/1/50
Maximum power input
W
35
8 - Technical Data
(*)
The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum lenght of the power supply line.
8.3 Electrical data
8.3.1 Compressor electrical data
EWFAIB
20
25 3
0
Power supply
V/ph/Hz
400 ± ( 10%)/3/50
Number
1
Maximum power input
kW
10.8
13.0
13.0
Nominal current input
A
15.0
18.0
20.0
Maximum current input
A
19.7
24.9
24.9
Crankcase heater (230±(10%)/1/50)
W
40
8.3.2 Fan electrical data
EWFAIB
20
2
5
3
0
Power supply
V/ph/Hz
230 ± ( 10%)/1/50
Number
2
Maximum power input
kW
0.3+0.3
0.3+0.3
0.3+0.3
Nominal current input
A
1.8+1.8
1.8+1.8
1.8+1.8
8.3.3 Pump electrical data
EWFAIB
20
2
5
3
0
Power supply
V/ph/Hz
400 ± ( 10%)/3/50
Number
1
Maximum power input
kW
0.65
0.65
0.65
Nominal current input
A
1.6
1.6
1.6
Summary of Contents for EWFAIB
Page 20: ...19 English Electrical Connections 4 Installation...
Page 24: ...23 English 6 EWFAIB Control 6 4 2 Set menu 6 4 3 tP menu...
Page 25: ...24 6 EWFAIB Control 6 4 4 I O menu...
Page 26: ...25 English 6 4 5 Err menu 6 EWFAIB Control 6 4 6 LOG menu 6 4 7 PAr menu...
Page 27: ...26 6 EWFAIB Control 6 4 8 PSS menu...
Page 29: ...28 6 EWFAIB Control 6 5 1 3 Operating condition...
Page 42: ...41 English 8 5 Space Requirements 8 Technical Data 800 mm 400 mm 200 mm 200 mm 200 mm...