53
ENCLOSED DOCUMENTS
Table “A”: Technical Data
EQU-PF Model
270
280
290
2100
2115
2130
2145
2160
Nominal cooling capacity (*)
kW
70,3
79,5
88,0
101,2
114,5
126,0
143,0
161,0
E.E.R. (3
rd
step, 100%)
2,60
2,68
2,60
2,50
2,68
2,68
2,64
2,67
E.E.R. (3
rd
step, 100%)
EN 14511 05/11 (250kPa residual)
3,27
3,28
3,12
3,15
3,33
3,24
3,32
3,26
E.S.E.E.R.
3,25
3,47
3,25
2,98
3,35
3,48
3,30
3,46
E.S.E.E.R. +
3,75
4,02
3,77
3,44
3,89
4,00
3,80
3,99
E.S.E.E.R. EN 14511 05/11 (250kPa residual)
5,56
6,02
5,86
5,74
5,43
5,42
5,32
5,37
E.S.E.E.R + EN 14511 05/11 (250kPa residual)
6,42
6,97
6,79
6,63
6,30
6,24
6,13
6,19
Sound power level (3
rd
step, 100%) (***)
dB(A)
85
85
86
88
88
88
89
89
Scroll/step compressor
n°
2/3
2/2
2/3
2/3
2/3
2/2
2/3
2/2
Circuits
n°
1
1
1
1
1
1
1
1
Fans
n° x kW
2x2.13
2x2.13
2x2.32
3x2.33
3x2.12
3x2.16
4x2.25
4x2.25
Fan nominal air flow
m³/h
26000
26000
27000
39000
39000
39000
52000
52000
Fan maximum available static head
Pa
250
250
250
250
250
250
250
250
Water side heat exchanger water content
l
5,0
6,1
6,1
6,9
8,4
8,4
9,9
11,1
Water side heat exchanger nominal flow (*)
Water side heat exchanger
m³/h
kPa
12,1
42
13,6
37
15,1
45
17,4
47
19,6
42
21,6
51
24,5
49
27,6
50
nominal pressure drops (*)
P1 residual head (*)
kPa
134
129
119
110
106
90
141
122
P2 residual head (*)
kPa
254
247
248
238
232
214
270
249
ASP1 residual head (*)
kPa
131
125
117
108
103
86
136
117
ASP2 residual head (*)
kPa
251
243
246
236
229
211
266
244
Water tank content (ASP1/ASP2)
l
250
250
250
250
450
450
450
450
Amount of R410A refrigerant
See serial number plate
Amount of Polyester oil
See compressor plate
Electrical data
270
280
290
2100
2115
2130
2145
2160
Absorbed power (*) (■)
kW
27,0
29,7
33,8
40,5
42,7
47,0
54,2
60,4
Pump absorbed power (P1/ASP1) / (P2/ASP2)
kW
1,1/2,2
1,1/2,2
1,5/3,0
1,5/3,0
1,5/3,0
1,5/3,0
2,2/4,0
2,2/4,0
Electrical power supply
V-ph-Hz
400
– 3+N – 50
Auxiliary power supply
V-ph-Hz
230
– 1+N – 50
Control power supply
V-ph-Hz
24
– 1 – 50
Nominal current (■)
A
47,3
51,9
54,0
67,6
77,6
84,5
95,0
106,6
Maximum current
(■)
A
64,3
68,7
72,7
85,4
91,2
100,2
116,1
127,1
Starting current (■)
A
207
212
262
313
319
327
368
382
Pump absorbed current (P1/ASP1) / (P2/ASP2)
A
2,6/5,0
2,6/5,0
3,5/6,0
3,5/6,0
3,5/6,0
3,5/6,0
5,0/8,1
5,0/8,1
Dimensions
270
280
290
2100
2115
2130
2145
2160
Width (a)
mm
1100
1100
1100
1100
1100
1100
1100
1100
Height (b)
mm
1920
1920
1920
1920
2320
2320
2320
2320
Depth (c)
mm
3650
3650
3650
3650
4450
4450
4450
4450
Heat exchanger inlet/outlet connections
Ø
2”
2”
2”
2”
2”
2”
2”
2”
DS/RC100 inlet/outlet connections
Ø
2”
2”
2”
2”
2”
2”
2”
2”
(*)
In the following conditions: Condenser inlet
air temperature 35°C; chilled water temperature
7°C; temperature differential at evaporator 5°C.
(***)
Sound power level in dB(A) on the basis of
measurements taken in accordance with RS
6/C/005-2009. The noise data refers to the units
without the pump.
(■)
Pumps excluded.
Nota Bene:
The E.E.R. and C.O.P calculation does not
consider the absorption of the pumps.
The EER, ESEER and COP calculations
according to EN 14511 05/11 (250kPa residual)
refer to the versions without pumps.
The starting current reduces by 25% with the
SFS accessory
The machine decreases its noise below the
nominal value indicated in the table when the
outdoor air temperature is below 35°C and
condensation control is present.
If the INS accessory is present, the sound
power Lw decreases by 2 dB(A).