ENCLOSED DOCUMENTS
52
A1
TECHNICAL DATA
Table “A”: Technical Data
EQU-PF Model
233
238
245
250
260
265
Nominal cooling capacity (*)
kW
32,5
38,8
44,2
51,3
59,2
64,0
E.E.R. (3
rd
step, 100%)
2,36
2,93
2.46
2,29
2,37
2,38
E.E.R. (3rd step, 100%) EN 14511 05/11 (250kPa residual)
2,95
3,65
2,90
3,06
3,05
3,01
E.S.E.E.R.
3,07
3,81
3,08
2,86
2.96
2,97
E.S.E.E.R. +
3,44
4,25
3,57
3,30
3,41
3,48
E.S.E.E.R EN 14511 05/11 (250kPa residual)
5,35
6,02
5,59
5,14
5,33
5,36
E.S.E.E.R + EN 14511 05/11 (250kPa residual)
5,99
6,72
6,48
5,94
6,13
6,28
Sound power level (3
rd
step, 100%) (***)
dB(A)
82
82
83
85
85
85
Scroll/step compressor
n°
2/2
2/2
2/3
2/3
2/3
2/3
Circuits
n°
1
1
1
1
1
1
Fans
n° x kW
1x2.08
1x2.08
1x2.10
2x2.15
2x2.23
2x2.23
Fan nominal air flow
m³/h
13000
13000
13000
26000
26000
26000
Fan maximum available static head
Pa
250
250
250
250
250
250
Water side heat exchanger water content
l
3,20
3,20
3,80
4,40
5,10
5,70
Water side heat exchanger nominal flow (*)
m³/h
5581
6674
7600
8800
10200
11000
Water side heat exchanger nominal pressure drops (*)
kPa
27,6
56,0
32,0
32,0
33,0
31,0
P1 residual head (*)
kPa
134
130
122
114
102
92
P2 residual head (*)
kPa
231
227
195
190
184
167
ASP1 residual head (*)
kPa
107
87
113
103
88
75
ASP2 residual head (*)
kPa
202
184
186
179
163
150
Water tank content (ASP1/ASP2)
l
150
150
150
150
150
150
Amount of R410A refrigerant
See serial number plate
Amount of Polyester oil
See compressor plate
Electrical data
233
238
245
250
260
265
Absorbed power (*)
(■)
kW
13,8
13,2
17,9
22,4
25,0
26,9
Pump absorbed power (P1/ASP1) / (P2/ASP2)
kW
0,70/1,5
0,70/1,5
0,70/1,5
0,70/1,5
0,70/1,5
0,70/1,5
Electrical power supply
V-ph-Hz
400
– 3+N – 50
Auxiliary power supply
V-ph-Hz
230
– 1+N – 50
Control power supply
V-ph-Hz
24
– 1 – 50
Nominal current (■)
A
21,8
25,4
25,1
31,9
37,0
41,3
Maximum current (■)
A
27,8
31,4
36,7
45,7
50,4
55,2
Starting current (■)
A
117
117
132
152
218
224
Pump absorbed current (P1/ASP1) / (P2/ASP2)
A
2,2/3,5
2,2/3,5
5,1/8,6
5,1/8,6
5,1/8,6
5,1/8,6
Dimensions
233
238
245
250
260
265
Width (a)
mm
870
870
870
870
870
870
Height (b)
mm
1920
1920
1920
1920
1920
1920
Depth (c)
mm
2650
2650
2650
2650
2650
2650
Heat exchanger inlet/outlet connections
Ø
1-
1/4”
1-
1/4”
1-
1/4”
1-1/4
”
1-
1/4”
1-
1/4”
DS/RC100 inlet/outlet connections
Ø
1-
1/4”
1-
1/4”
1-
1/4”
1-
1/4”
1-
1/4”
1-
1/4”
(*)
In the following conditions: Condenser inlet
air temperature 35°C; chilled water temperature
7°C; temperature differential at evaporator 5°C.
(***)
Sound power level in dB(A) on the basis of
measurements taken in accordance with RS
6/C/005-2009 and UNI EN-ISO 9614/1. The
noise data refers to the units without the pump.
(■)
Pumps excluded.
Note:
The E.E.R. and C.O.P calculation does not
consider the absorption of the pumps.
The EER, ESEER and COP calculations
according to EN 14511 05/11 (250kPa residual)
refer to the versions without pumps.
The starting current reduces by 25% with the
SFS accessory
The machine decreases its noise below the
nominal value indicated in the table when the
outdoor air temperature is below 35°C and
condensation control is present.
If the INS accessory is present, the sound
power Lw decreases by 2 dB(A).