19
SECTION II: INSTALLATION AND MAINTENANCE
II.7.2
General conditions of the unit
YES
YES
YES
NO
NO
NO
YES
NO
II.7.2.1
Checking compressor oil level
YES
YES
NO
NO
II.7.2.2
Checking hydraulic connections
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
START
The general status of the unit is compliant!
START
The compressor is ready to start!
START
The hydraulic connection is compliant!
Danger!
Do not start the unit! Restore
the unit!
Restore or replace the component.
Are the water filters upstream the heat exchanger and the recovery unit in
good working order and installed correctly?
Restore or replace the component.
Are the flow meters (if installed) active and correctly connected?
Restore the rotation direction.
Do the pumps turn the right way?
Restore the water flow rate.
Is the water flow rate compliant with that indicated in the user manual?
Fill the circuits and/or bleed the air.
Are the circuits full of water and has any residual air been bled?
Correct the inlet-outlet direction.
Is the water inlet/outlet direction correct?
Adjust the connections.
Have the hydraulic connections been implemented according to the state-of-
the-art?
Activate pre-heating and wait 12 hours.
Was pre-heating activated at least 12 hours before start-
up?
Top-up as necessary
Is the oil level sufficient?
Is the unit damaged due to transport/installation?
Remove the obstructions.
Are the fan grilles free from obstructions?
Clean the finned coils.
Is the finned coil free from obstructions?
Restore the technical clearance distances indicated.
Have the technical clearance distances indicated in the manual been
respected?