EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
THERMOSTAT AND CONTROL
MCX-15 START UP
Regulation Parameters
Configuration
Temperature Regulation Entry
This is used to tell the system whether regulation will be applied to IN or OUT water temperature.
Calibration of the Regulation Probes.
Adjusts probe regulation values in the range between -99,9 and 99,9.
Set Point
Cooling Set point Temperature.
Sets the value of the operating Cooling Set point temperature in ºC, by default this value is set to 7ºC. Values can range between 6,0
and up to 17,0ºC.
Lower Limit Set point Temperature.
This is used to set the lowest limit of the Set point temperature in cooling more.
By default this value is 6,0ºC.
High Limit Set point Temperature.
This is used to set the highest limit of the Set point temperature in cooling more.
By default this value is 17,0ºC.
Heating Set point Temperature.
Sets the value of the operating Cooling Set point temperature in ºC, by default this value is set to 45ºC. Values can range between
35,0 and up to 55,0ºC.
Lower Limit Set point Temperature.
This is used to set the lowest limit of the Set point temperature in heating more.
By default this value is 35,0ºC.
High Limit Set point Temperature.
This is used to set the highest limit of the Set point temperature in heating more.
By default this value is 55,0ºC.
Compressors
Activation
Activation of compressor 1
Activates or disables compressor 1.
Activation of compressor 2
Activates or disables compressor 2.
AI1:
Regulation of INTAKE water.
AI2:
Regulation of OUTLET water.