UMXCBA/UMXCA
CONDENSER UNITS WITH
COMPRESSOR AND AXIAL FAN
TECHNICAL SPECIFICATIONS
UMXCBA / UMXCA
MODELS
801.1
1001.1
1201.1
1501.1
COOLING CAPACITY
Nominal cooling capacity
(1)
kW
25,9
31,2
38,1
42,9
Total absorbed power cooling
(1)
kW
8,8
9,8
12,5
14,3
EER coefficient cooling
---
2,94
3,19
3,05
3,01
HEATING CAPACITY
Nominal heating capacity
(2)
kW
27,3
30,7
39,5
43,6
Total absorbed power heating
(2)
kW
7,1
8,4
10,9
11,4
COP coefficient
---
3,85
3,67
3,63
3,82
REFRIGERANT
Type
---
R-410A
Charge
(3)
kg
6,5
7
8
8,3
Global warming potential (GWP)
(4)
---
2088
ELECTRICAL SPECIFICATIONS
Power supply
V / ~ / Hz
400 / 3+N / 50
Maximum absorbed current
A
27,9
29,9
38,6
44,9
Start current
A
145,4
145,4
162,2
201,3
COMPRESSOR
Type
---
Scroll
Number
---
1
Number of refrigerant circuit
---
1
Number of stages
---
1
Oil type
Danfoss POE oil 160SZ
Oil volume
L
3,3
3,3
3,3
3,6
REFRIGERANT CONNECTIONS
Liquid line diameter circuit 1
‘’
5/8
Gas line diameter circuit 1
‘’
1 1/8
Liquid line diameter circuit 2
‘’
-
-
-
-
Gas line diameter circuit 2
‘’
-
-
-
-
FAN
Type
---
Outdoor Axial Rotor
Nominal air flow
m
3
/h
17700
17700
19700
19700
Available static pressure
Pa
0
Number
---
1
Diameter
mm
710
710
800
800
Power
Δ/Υ
kW
1,25 / 0,97
1,25 / 0,97
1,90 / 1,20
1,90 / 1,20
Speed
Δ/Υ
r.p.m.
950 / 825
950 / 825
890 / 690
890 / 690
DIMENSIONS AND WEIGHT
Length
mm
1200
1200
1200
1200
Width
mm
1050
1050
1050
1050
Height
mm
1470
1470
1470
1470
Weight
kg
256
277
283
287
(1)
Calculated according to the UNE-EN-14511 standard, for indoor temperature conditions of 27ºC B.S. / 19ºC B.H. and 35ºC
outdoor temperature.
(2)
Calculated according to the UNE-EN-14511 standard for indoor temperature levels lower than 20ºC and outdoor temperature
levels of 7ºC B.S. / 6ºC BH. (3) The basic charge does not include the refrigeration lines. The standard equipment is delivered
with a nitrogen charge. The refrigerant is included only when the equipment is delivered with a Flare valve which is available as
an option.
(4)
GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated over a period of 100 years.