5.
Close the lever completely and secure the power supply. If the lever
cannot be moved, reorient the power supply, and then reinsert it into the
slot.
6.
Connect the power cable to the power supply, and then secure the cable
using the cable holder.
7.
Confirm that the red
ALM
LED is off at the power supply and the green
RDY
LED is on.
Note:
If the
ALM
LED is on and the status of the power supply is
Normal, go to the Customer Contact Us page at
support.hds.com/en_us/contact-us.html
.
If the red
ALM
LED does not go off after more than 30 minutes following
replacement of the power supply, remove the power supply, wait at least
30 seconds, and then reinstall it.
Replacing a power supply for a FMD drive tray
Caution:
Be sure to replace the faulty power supply. If you replace the
operational power supply, the system will go down.
Caution:
A short-circuit can cause a fire. Never insert metal or other objects
into the cable connector; otherwise, a short-circuit can occur.
Note:
Power supply unit #1 and power supply unit #2 are installed in
opposite directions.
Before you begin
• Wear a wrist strap connected to the storage system to prevent part
failures caused by static electricity. Do not remove the wrist strap until you
finish the procedure.
• Confirm that the storage system power is turned on.
• Confirm that the red
ALM
LED for the power supply unit to be replaced is
on.
Note:
If the red
ALM
LED is on at both power supplies, do not perform this
procedure, even if the status of the power supplies is
Normal
. Go to the
Customer Contact Us page at
https://support.hds.com/en_us/contact-
.
Procedure
1.
Disconnect the power cable from the power supply to be replaced.
Remove the cable holder to disconnect the power cable from the power
supply.
150
Replacing a power supply
Service Guide for VSP Gx00 and VSP Fx00 Models
Summary of Contents for Virtual Storage Platform F400
Page 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...