73
Protection Control Code and Retry Control Code
Indication
(SEG1)
Protection Control
Remark
Pressure Ratio Protection Control
To control the compressor frequency for prevention of operation with high/low
pressure ratio.
High Pressure Increase Protection
Control
To control the compressor frequency for prevention of high pressure
increase.
Inverter Current Protection Control
To control the compressor frequency for prevention of inverter current
increase in the outdoor unit during operation.
Inverter Fin Temperature Increase
Protection Control
To control the compressor frequency for prevention of inverter fin temperature
increase. The inverter fin temperature is detected at the inverter PCB.
Discharge Temperature Increase Protection
Control
To control the compressor frequency for prevention of discharge gas
temperature increase during operation.
Low Pressure Decrease Protection
Control
To control the compressor frequency for prevention of low pressure decrease.
High Pressure Decrease Protection Control
To control the compressor frequency for prevention of high pressure
decrease, which would interrupt smooth refrigerant distribution to indoor units
with different height and oil supply to the compressor.
Demand Current Control
To control the compressor frequency for fixing the inverter primary current
around the set value (40~100% of rated current for cooling).
Low Pressure Increase Protection
Control
To control the compressor frequency for prevention of low pressure increase.
Inverter Trip Retry
To stop the unit operation temporarily for protection of the compressor and
inverter. The operation will be restarted or stopped depending on the retry
frequency.
In
sufficient Voltage/Open Phase
Detection Retry
2. Troubleshooting Procedures
2.1 Alarm Code Indication of Wired Controller
Protection control code is displayed on the wired controller when a protection control is activated.
Refrigerant System No. 00
(Scope: 00~63)
Indoor Unit No.
01
(Scope: 00~63)
Alarm Code No.04
Press the Button Back
to Main Interface
Alarm Sign
Blinking
TROUBLESHOOTING
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...