Maintenance
Technical Catalogue
TCGB0051 rev 0 - 09/2009
74
11.11.1. Safety and control device setting
Model
RCUE
CLG2
40
50
60
80
100
120
For Compressor
Manual reset, non-adjustable (one switch for each compressor motor )
High Pressure Switch
Cut-Out
MPa
2,80
2,80
2,80
2,80
2,80
2,80
Low Pressure Switch
Electronic control
(Pressure Sensor)
Cut-Out
MPa
0,05
0,05
0,05
0,05
0,05
0,05
Internal Thermostat for Compressor
Manual reset, non-adjustable (one switch for each compressor motor )
Cut-Out
°C
115
115
115
115
115
115
Cut- In
°C
93
93
93
93
93
93
Compressor Motor (380-415V/50Hz)
Fuse
A
125
125
160
125
125
160
Manual reset, adjustable (one three-phase set for each compressor motor )
Thermal Relay
A
54
65
80
54
65
80
Manual reset, adjustable (one three-phase set for each compressor motor )
Magnetic Circuit Protector (Option)
A
90
107
135
90
107
135
Oil Heater
One heater for each compressor motor
Capacity
W
150
150
150
150
150
150
Discharge Gas (Electronic Control)
(One for each cycle)
Cut-Out
°C
140
140
140
140
140
140
CCP Timer
Non-adjustable (one timer for each compressor)
Setting Time
S
180
180
180
180
180
180
Star-Delta
S
5
5
5
5
5
5
Unloading during Starting
S
30
30
30
30
30
30
For Refrigerant Circuit
(One for each circuit )
Pressure Relief Valve
MPa
3
3
3
3
3
3
Setting Pressure
Freeze Protection Thermostat
(One for each water cooler )
Cut-Out
°C
2
2
2
2
2
2
Summary of Contents for SAMURAI CLG2
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 46: ......
Page 62: ......
Page 66: ......
Page 82: ......
Page 94: ...Drawings Technical Catalogue TCGB0051 rev 0 09 2009 94 14 2 4 Main printed circuit board ...
Page 95: ...Drawings Technical Catalogue 14 95 TCGB0051 rev 0 09 2009 14 2 5 Relays printed circuit board ...
Page 98: ......
Page 112: ......
Page 116: ......
Page 117: ......