Control System
Technical Catalogue
10
65
TCGB0051 rev 0 - 09/2009
10.2. Standard operating sequence for RCUE80CLG2, RCUE100CLG2 and RCUE120CLG2
Control Stage
Control Devices
Starting Control
Capacity Control
Safety Devices
Shut Down
Main Power Switch
OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON OFF
Chilled Water Pump
-
OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON OFF OFF
Condenser Water
Pump
-
OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON OFF OFF
Operation Switch (ON/
OFF)
-
-
-
ON
-
-
-
-
-
-
-
-
-
-
-
-
-
-
OFF
-
OFF
-
Controller
Load
Up
-
-
-
-
-
-
-
-
o
o
-
-
-
-
-
-
o
o
-
-
-
-
Neutral
-
-
-
-
-
-
-
-
-
-
o
-
-
-
-
o
-
-
-
o
-
-
Load
Down
-
-
-
-
-
-
-
-
-
-
-
o
o
o
o
-
-
-
-
-
-
-
Safety
Devices
No.1
CLS CLS CLS CLS CLS CLS CLS CLS
CLS
CLS CLS
CLS
CLS
CLS CLS
CLS
OPN
OPN CLS CLS CLS CLS
No.2
CLS CLS CLS CLS CLS CLS CLS CLS
CLS
CLS CLS
CLS
CLS
CLS CLS
CLS
CLS
OPN CLS CLS CLS CLS
Power Supply
Indicator
OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON OFF
Operation
Indicator
OFF OFF OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON OFF ON OFF OFF
Alarm
Indicator
OFF OFF OFF ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF OFF OFF OFF
Oil Heater
CH1
OFF ON
ON
ON OFF OFF OFF OFF
OFF
OFF OFF
OFF
OFF
OFF ON
OFF
ON
ON
ON
ON
ON OFF
CH2
OFF ON
ON
ON
ON
ON OFF OFF
OFF
OFF OFF
OFF
OFF
OFF ON
OFF
OFF
ON
ON
ON
ON OFF
Compressor
Motor
STA
DLT
STA
DLT
DLT
DLT DLT
DLT
DLT
DLT
DLT
DLT
MC1
OFF OFF OFF OFF (ULD) (ULD) (ULD) (ULD) (ULD) (FLD) (FLD) (ULD)
(ULD) (ULD) OFF (ULD)
OFF
OFF OFF (FLD) OFF OFF
15% 15% 15% 15% 15~99% 100% 100% 15~99% 15~99% 15%
15~99%
100%
STA
DLT
DLT
DLT DLT
DLT
DLT
DLT
DLT
DLT
DLT
MC2
OFF OFF OFF OFF OFF OFF (ULD) (ULD) (ULD) (FLD) (FLD) (ULD)
(ULD) (ULD) OFF (ULD)
(ULD) OFF OFF (FLD) OFF OFF
15% 15% 15~99% 100% 100% 15~99% 15~99% 15%
15~99% 15~99%
100%
Solenoid
Valve
SV11
OFF OFF OFF ON
ON
ON
ON
ON
OFF
OFF OFF
OFF
OFF
OFF ON
OFF
OFF
OFF OFF OFF OFF OFF
SV12
OFF OFF OFF OFF OFF OFF OFF OFF
OFF
OFF OFF
ON
OFF
ON OFF
OFF
OFF
OFF OFF OFF OFF OFF
SV13
OFF OFF OFF OFF OFF OFF OFF OFF
ON
ON OFF
OFF
OFF
OFF OFF
OFF
OFF
OFF OFF OFF OFF OFF
SV21
OFF OFF OFF ON
ON
ON
ON
ON
OFF
OFF OFF
OFF
OFF
OFF ON
OFF
OFF
OFF OFF OFF OFF OFF
SV22
OFF OFF OFF OFF OFF OFF OFF OFF
OFF
OFF OFF
ON
OFF
ON OFF
OFF
OFF
OFF OFF OFF OFF OFF
SV23
OFF OFF OFF OFF OFF OFF OFF OFF
ON
ON OFF
OFF
OFF
ON OFF
OFF
ON
OFF OFF OFF OFF OFF
Time Schedule
CLS: Close
OPN: Open
STA: Star
DLT: Delta
ULD: Unload
FLD: Full Load
The compressor which started finally will be started first
Minimum 3min.
3min.
60sec.
30sec.
5sec.
5sec.
Summary of Contents for SAMURAI CLG2
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 46: ......
Page 62: ......
Page 66: ......
Page 82: ......
Page 94: ...Drawings Technical Catalogue TCGB0051 rev 0 09 2009 94 14 2 4 Main printed circuit board ...
Page 95: ...Drawings Technical Catalogue 14 95 TCGB0051 rev 0 09 2009 14 2 5 Relays printed circuit board ...
Page 98: ......
Page 112: ......
Page 116: ......
Page 117: ......