Controller Adjustment
Technical Catalogue
TCGB0051 rev 0 - 09/2009
50
SWITCH POSITION
ON
OFF
ON
ON
OFF
OFF
High Cut Check (Fan Stop for Checking)
(NOT AVAILABLE)
Chilled Water Temperature Setting
(STANDARD: “+07”)
Defrosting Set by Ambient Temperature (Heat Pump)
(NOT AVAILABLE)
Continuous Capacity Control Setting
(STANDARD)
Compressor starting Delay Time (STANDARD: 3
min) High Cut Check Setting (Stop Fan Selection:
NOT AVAILABLE.)
Mode Set Switch A
(DEPEND ON MODEL)
Manual Defrost (Heat Pump)
(NOT AVAILABLE)
Optional Function B
(STANDARD: ALL OFF)
Optional Function C
(STANDARD: ALL OFF)
Mode Set Switch B
Local/Remote Changeover Switch
(STANDARD: “Local”)
Cool/Heat Changeover Switch
(STANDARD: “Cool”)
Current Limitation
(Not Available)
Neutral Zone Setting
(STANDARD: “3”)
Hot Water Temperature Setting for Heat Pump
(NOT AVAILABLE)
Optional Function A (Outernals signals, Self-
Checking mode)
(STANDARD: ALL OFF)
Pump Operation
(STANDARD: OFF)
LED
PUSH
BUTTON
SWITCH
7 SEGMENTS
Cool
Heat
Local
Remote
8.1. PCB Drawing