Model Selection
Technical Catalogue
TCGB0051 rev 0 - 09/2009
106
15.4. Sound Data
¡
Standard Models
Model
Sound Pressure Level (dB)
Frequency Band (Hz)
Overall
(dBA)
63
125
250
500
1000
2000
4000
8000
RCUE40CLG2
77
69
71
63
62
61
53
37
68
RCUE50CLG2
74
76
71
64
65
64
51
35
69
RCUE60CLG2
77
69
67
62
68
66
53
35
71
RCUE80CLG2
77
70
70
71
62
64
50
39
71
RCUE100CLG2
79
71
70
67
68
67
54
38
72
RCUE120CLG2
80
72
70
65
71
69
56
38
74
Model
Sound Power Level (dB)
Frequency Band (Hz)
Overall
(dBA)
63
125
250
500
1000
2000
4000
8000
RCUE40CLG2
92
84
86
78
77
76
68
52
83
RCUE50CLG2
89
91
86
79
80
79
66
50
84
RCUE60CLG2
92
84
82
77
83
81
68
50
86
RCUE80CLG2
92
85
85
86
77
79
65
54
86
RCUE100CLG2
95
87
86
83
84
83
70
54
88
RCUE120CLG2
96
88
86
81
87
85
72
54
90
NOTE:
1. The sound pressure is based on the following conditions.
- 1 meter from the control panel surface and 1.5 meter from the floor level.
- Voltage of the power source is 380V.
- The above data was measured in an anechoic chamber, so that reflected sound should be taken into consideration in the
field.
2. Operating conditions are as follows.
Standard Models: Cooler Water Inlet/Outlet Temperature 12/7 °C, Condensing Temperature 45 °C.
Summary of Contents for SAMURAI CLG2
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 46: ......
Page 62: ......
Page 66: ......
Page 82: ......
Page 94: ...Drawings Technical Catalogue TCGB0051 rev 0 09 2009 94 14 2 4 Main printed circuit board ...
Page 95: ...Drawings Technical Catalogue 14 95 TCGB0051 rev 0 09 2009 14 2 5 Relays printed circuit board ...
Page 98: ......
Page 112: ......
Page 116: ......
Page 117: ......