Initial troubleshooting
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
observed failure
Cause
Check item
Action
(Turn off the main switch)
System controller cable disconnected
Connect the cable
Replace the cable or repair the
cable
One (or several) phase failure, or inverted phase order ("
” alarm).
Only in three phase unit.
Check the connection of R,S
and T phase.
Reorder the phases
Failure of remote/local switch or remote/local switch set at “local”
Check remote/local switch
Turn the switch to “remote” or
replace switch
Deficient contact at terminal
controller connectors
Insufficient connection or incorrect
connection of the Yutaki unit PCB
Check the connectors and
terminals
Remove rust, dust or any
contaminants, check the
correct tightening of the
terminals
Insufficient connection
or incorrect connection of the terminal
in remote controller
Failure of the system controller
Refer to “Troubleshooting of system controller”
Undefined PCB failure
Unconnected wires to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB through its self-
diagnostic mode
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in
"TEST RUN"