4 Capacities and selection data
Combinability range
TCGB0136 rev.1 - 05/2021
48
4.1 Combinability range
4.1.1 Connected number of indoor units
Range of operation capacity control from 90 to 100% for 1 or 2 indoor units (RAS-3HVRC2) and 90 up to 115% for 1 to 4
indoor units (RAS-(4-6)H(V)(R/N)(C/P)2E).
Outdoor unit
Minimum combination
capacity (HP)
Maximum combination
capacity (HP)
Maximum Combination
quantity
Minimum indoor unit
capacity (HP)
RAS-3HVRC2
2.7
3
2
0.8
RAS-4H(V)R(C/P)2E
3.6
4.6
4
0.8
RAS-5H(V)R(C/P)2E
4.5
5.75
4
0.8
RAS-6H(V)R(C/P)2E
5.4
6.9
4
0.8
RAS-4H(V)N(C/P)2E
3.6
4.6
4
0.8
RAS-5H(V)N(C/P)2E
4.5
5.75
4
0.8
RAS-6H(V)N(C/P)2E
5.4
6.9
4
0.8
?
N O T E
• In case of installation in cold territories (where Outdoor Temperature may fall below -5ºC) or in places where Heating load is large,
install a number of units with a connected capacity ratio under 100%.
• Please check the piping chapter for other restrictions and limitations to adequate the combinability and the number of indoor units
installed.
“9. Piping work and refrigerant charge”
for detailed information and additional remarks about combinability.