SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Outdoor Unit
RAM-90NP5E
●
Carefully read through the procedures of proper
installation before starting installation work.
●
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
SAFETY PRECAUTION
●
Read the safety precautions carefully before operating the unit.
●
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user’s guide.
!
!
WARNING
!
CAUTION
!
●
Flare nut must use a torque wrench without fail. Tighten with the speci
fi
ed tightening torque. If the
fl
are nut is
tightened too much, after a long period of time, the
fl
are nut breaks, Gas leakage, stagnation, touching
fi
re, rarely
cause ignition.
●
Sharp bending of the pipe use the polyethylene rod, bend not crushed the pipe. Gas leakage from the crushed part,
stagnation, touching
fi
re, rarely cause ignition.
●
Please request your sales agent or quali
fi
ed technician to install your unit. Water leakage, short circuit or
fi
re may
occur if you do the installation work yourself.
●
Please observe the instructions stated in the installation manual during the process of installation. Improper installation
may cause water leakage, electric shock and
fi
re.
●
A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to
fl
ow
between the refrigerating system parts. A vacuum valve shall be provided to evacuate the interconnecting pipe and/
or any uncharged refrigerating system part.
●
Mechanical connectors used indoors shall comply with ISO 14903. When mechanical connectors are reused indoors,
sealing parts shall be renewed. When
fl
ared joints are reused indoors, the
fl
are part shall be re-fabricated.
●
Refrigerant tubing shall be protected or enclosed to avoid damage.
●
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units.
If not, the units may collapse and impose danger.
●
Observe the rules and regulations of the electrical installation and the methods described in the installation manual
when dealing with the electrical work. Use power cables approved by the authorities of your country.
●
Be sure to use the speci
fi
ed wire for connecting the indoor and outdoor units. Please ensure that the connections
are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may
cause over-heating and
fi
re.
●
Please use the speci
fi
ed components for installation work. Otherwise, the units may collapse or water leakage,
electric shock and
fi
re may occur.
●
Be sure to use the speci
fi
ed piping set for R32. Otherwise, this may result in broken copper pipes or faults.
●
When installing or removing an air conditioner, only speci
fi
ed refrigerant (R32) shall be allowed, do not allow air or
moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally
high so that a rupture may be caused.
●
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with
fi
re,
a poisonous gas may occur. Be aware that refrigerants may not contain an odour.
●
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant
gas leaks into the room, coming into contact with
fi
re in the fan-driven heater, space heater, etc., a poisonous gas
may occur.
●
Unauthorized modi
fi
cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali
fi
ed
air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and
fi
re, etc.
FOR SERVICE PERSONNEL ONLY
The Choice of Mounting Site
(Please note the following matters and obtain permission from customer before installation).
Dimension of Mounting Stand
of the Outdoor unit
(unit : mm)
Names of Outdoor Components
●
A circuit breaker or fuse must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
The external switch shall be incorporated to completely disconnect from power supply. It should disconnect all
poles, and a contact separation of at least 3mm must be present.
●
Do not install the unit near a location where there is
fl
ammable gas. The outdoor unit may catch
fi
re if
fl
ammable gas leaks around it.
●
Do not install the indoor unit in a machine shop or kitchen where vapor from oil or its mist
fl
ows to the indoor
unit. The oil will deposit on the heat exchanger, thereby reducing the indoor unit performance and may deform
and in the worst case, break the plastic parts of the indoor unit.
●
Please ensure smooth
fl
ow of water when installing the drain hose.
●
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
(
mark is tool exclusive use for R32)
●
+ – Screwdriver
●
Measuring Tape
●
Knife
●
Saw
●
Pipe Cutter
●
Hexagonal Wrench Key (
4mm)
●
Power Drill (ø 65mm ~ ø 80mm)
Vacuum Pump
●
Pliers or Wrench
●
Torque Wrench
Vacuum
Pump Adaptor
●
Flare Tool
Gas Leakage Detector
Manifold Valve
Charge Hose
●
Reamer
●
File
Figure showing the Installation of Outdoor Unit.
●
This unit is chargeless up 35m pipe length.
●
Installation of pipe length less than minimum pipe length
requirement (3 meters) may generate an abnormal sound.
CAUTION
<
IA0000: A
>
This symbol shows that this
equipment uses a
fl
ammable
refrigerant.
If the refrigerant is leaked, together
with an external ignition source,
there is a possibility of ignition.
This symbol shows that the
Operation Instructions should be
read carefully.
This symbol shows that a service
personnel should be handling this
equipment with reference to the
Installation Manual.
This symbol shows that there
is information included in
the Operation Manual and/or
Installation Manual
WARNING
CAUTION
CAUTION
CAUTION
!
BURST HAZARD
Do not allow air, etc. to
get into refrigerant cycle
(piping)
RISK OF EXPLOSION
Compressor must be
stopped before removing
refrigerant pipes.
All service valve must be
fully closed after pumping
down operation.
WARNING
●
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the
manufacturer. Any un
fi
t method or using incompatible material may cause product damage, burst and serious
injury.
●
The appliance/pipe-work shall be stored in a well ventilated room with indoor
fl
oor area larger than A
min
[refer
to Table 1] and without any continuously operating ignition source. Keep away from open
fl
ames, any operating
gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
●
The appliance/pipe-work shall be installed, and/or operated in a room with
fl
oor area larger than A
min
[refer to
Table 1] and keep away from ignition sources, such as heat/spark/open
fl
ame or hazardous areas such as gas
appliances, gas cooking, reticulated gas supply systems or electric cooking appliances, etc.
●
Do not pierce or burn as the appliance/pipe-work is pressurized. Do not expose the appliance/pipe-work to heat,
fl
ame, sparks, or other sources of ignition. Else, it may explode and cause injury or death.
WARNING
!
Table 1: Minimum Floor area of the room A
min
(m
2
)
Minimum Floor Area of the room
A
min
(m
2
)
RAF-**RXE
RAD-**QPE
RAD-**RPE
RAI-**RPE
RAK-**QPE
RAK-**RXE
RAK-**RPE
Max
refrigerant
charge
amount
(kg)
Max
Piping
Length
(m)
Outdoor
Model
RAM-90NP5E
35
2.40
5.49
3.68
3.68
49.42
WARNING
!
●
The Outdoor unit must be mounted at a location which can support
heavy weight. Otherwise, noise and vibration will increase.
CAUTION
!
●
Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.
●
The air blown out of the unit should not point directly to animals
or plants.
●
The clearances of the unit from top, left, right and front are
speci
fi
ed in
fi
gure below. At least 3 of the above sides must be
open air.
●
Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.
●
Do not install at a location where there is
fl
ammable gas, steam,
oil and smoke.
●
The location must be convenient for water drainage.
●
Place the Outdoor unit and its connecting cord at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.
●
Do not install outdoor unit facing strong wind direction. It may
damage the fan motor.
●
Do not install the outdoor unit in a place where small animals
may build their nests. If small animal goes inside the unit and
touches the electrical parts, failure of the unit, smoke or
fi
re may
be caused. Request your customer to keep the surrounding of
the unit is clean.
OUTDOOR UNIT
1. Proper place for installation
1.1 Outdoor unit
(1) Keep the space around the unit for maintenance and avoiding the effects of hindrance for normal ventilation of the
unit.
(2) The northern or eastern side of the building is better to install. At the installation on the southern or western side
unavoidably, some blind should be set up for the unit. (In this case, the blind must not obstruct the ventilation of
the unit.)
(3) You’d better not put the unit at a place where is full of dirt and at a place where is wet in the rain.
(4) Place as near as possible to the indoor unit.
(5) Install the unit in a stable place to minimize vibration or noise.
(6) After arranging the cords and pipes, secure them in place.
●
This appliance must be earthed.
●
Power is supplied through outdoor unit, do not connect power source to indoor unit.
WARNING
!
2.
In the electrical installation a separator with a contact gap of more than 3mm has to be installed. During cleaning or service
the set has to be switched off with this separator.
Height difference
Height difference between indoor units should not be
more than 5m.
Piping length
(L1 + L2 + L3 + L4 + L5) = Maximum 75m
Minimum piping length for each indoor unit is 3m.
Maximum piping length for one indoor unit is 25m.
In case the pipe length is more than 35m, add refrigerant
R32 at 15 gram per every meter exceeds
Flare adaptor for piping
The
fl
are adaptor for piping is required
depending on combination of indoor units.
●
ø9.52 (3/8”)
➝
ø 12.7 (1/2”)
Parts number TA261D-4 001
●
ø12.7(1/2”)
➝
ø 9.52 (3/8”)
Parts number TA261D-6 002
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional
fl
are adaptor for piping is necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional
fl
are adaptor for piping is necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(5kW unit: Optional
fl
are adaptor for piping is necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(1.8kW-3.5kW unit: Optional
fl
are adaptor for piping is necessary.)
One unit of 1.5kW, 1.8kW, 2.5kW, 3.5kW or 5.0kW
(1.8kW-3.5kW unit: Optional
fl
are adaptor for piping is necessary.)
Drain Pipe
1
3
Bush
Qty
No.
Item
10
11
!
** is refering to indoor model name.
Please face this side (suction side)
of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
BASE
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed water to exhaust.
In order to
fl
ow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above the ground as shown
fi
gure. Join the drain pipe to one hole.
At
fi
rst insert one portion of the hook to the base (Portion A), then pull the drain pipe in the direction shown by the arrow while inserting the
hook into the base. After installation, check whether the drain pipe cling to the base
fi
rmly.
When Using and Installing In Cold Areas
When the air conditioner is used in low temperature and in snowy conditions, water from the heat exchanger may freeze on the base surface
to cause poor drainage. When using the air conditioner in such areas, do not install the bushings. Keep a minimum of 250mm between the
drain hole and the ground. When using the drain pipe, consult your sales agent.
For more details, refer to the installation Manual for Cold Areas.
DRAIN PIPE
100 mm
ABOVE
BUSH
DRAIN PIPE
Do not use this valve. For factory use only.
Mount the Outdoor unit on stable ground to prevent vibration and increase of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side plate, pull the handle after releasing the hook by pulling it downward.
To the outdoor unit, up to
fi
ve indoor units can be connected until the total value of each units’s capacity reaches
15.5 kW.
The pipe connection ports of the outdoor unit and connectable indoor units are shown above.
[Outdoor unit installation]
CAUTION
●
Make sure to connect to two or more indoor units.
!
CAUTION
!