HITACHI CEILING CASSETTE-UNIT AIR 

CONDITIONER INSTALLATION MANUAL

Indoor Unit

+    –  Screwdriver   

 Measuring Tape   

 Knife

Saw

ø 65mm Power Drill  

 Hexagonal Wrench Key (    4mm)  

 Wrench (14, 17, 19, 22, 26, 27mm) 

  ●

  Gas Leakage Detector

Pipe Cutter 

    ●

 Vinyl Tape

Pliers

Flare Tool

Carefully read through the procedures of proper installation
before starting installation work.

  The sales agent should inform customers regarding the correct 

operation of installation.

Tools Needed For Installation Work

SAFETY PRECAUTION

 

Read the safety precautions carefully before operating the unit.

The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING ........ Incorrect methods of installation may cause death or serious injury.

CAUTION ......... Improper installation may result in serious consequence.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as 
described in the user’s guide.

!

!

WARNING

!

CAUTION

!

A circuit breaker or fuse must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3.5mm has to be installed in the power supply line to the outdoor unit.

 

Piping shall be suitable supported with a maximum spacing of 1m between the supports.

Do not install the unit near a location where there is 

fl

 ammable gas. The outdoor unit may

catch 

fi

 re  if 

fl

 ammable gas leaks around it.

 

For installation of front panel RAI-ECPP, please follow exactly the instruction in the manual.

Please ensure smooth 

fl

 ow of water when installing the drain hose.

  Please request your sales agent or quali

fi

 ed technician to install your unit. Water leakage, short circuit or 

fi

 re may occur if you do the installation work y

ourself

.

Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric
shock and 

fi

 re.

  Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose 

danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work.
Use power cables approved by the authorities of your country.

Be sure to use speci

fi

 ed wire for the connection indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are

inserted into the terminals. Improper insertion and loose contact may cause over-heating and 

fi

 re.

Please use the speci

fi

 ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock and 

fi

 re may occur.

Be sure to use the speci

fi

 ed piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.

  When installing or removing an air conditioner, only speci

fi

 ed refrigerant (R410A) shall be allowed, do not allow air or moisture to remain in the refrigeration 

cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with 

fi

 re, a poisonous gas may occur.

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into
contact with 

fi

 re in the fan-driven heater, space heater, etc., a poisonous gas may occur.

Unauthorized 

modi

fi

 cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali

fi

 ed air conditioner technician or electrician.

Improper repairs may result in water leakage, electric shock and 

fi

 re,  etc.

THE CHOICE OF MOUNTING SITE 

 (Please note the following matters and obtain permission from customer before installation).

WARNING

!

The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.

CAUTION

!

No nearby heat source and no obstruction near the air outlet is allowed.

The clearance distances from top, right and left are speci

fi

 ed  in 

fi

 gure  below.

The location must be convenient for water drainage and pipe connection with the outdoor unit.

To avoid interference from noise please place the unit and its remote controller at least 1m from the radio, television and inverter type 

fl

 uorescent  lamp.

To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless 
systems.

The installation height of indoor unit must be 2.3m ~ 3m. Installation above 3m will affect the performance of unit.

INDOOR UNIT

Names of Indoor Components

Insulation pipe for 

fl

 are  section

Qty

No.

Item

Figure showing the Installation of Indoor Unit.

2

Opening on ceiling and suspension bolt

1

(Unit : mm)

 

Need a connecting work for refrigerant pipe, drain pipe and connecting cable in the ceiling
after suspending the indoor unit. Arrange drain pipe, refrigerant pipe and connecting cable
in their installation position.

 

For 

fi

 nishing of opening on ceiling, arrange with builder in detail.

 

If ceiling is already completed, connecting cables between indoor and outdoor, piping and
drain piping must be done before 

fi

 tting indoor unit.

Wall Penetration and Installation of Protection Pipe

  Drill a ø 65mm hole on wall which is slightly tilted towards 

the outdoor side. Drill the wall at a small angle.

Cut the protection pipe according to the wall thickness.

Empty gap in the sleeve of protection pipe should be
completely sealed with putty to avoid dripping of rain
water into the room.

 

In case drain piping cannot be done smoothly due to obstacles, it can also be arranged
outside of the main unit as shown in the drawing below.

!

CAUTION

The rubber strap used for fixing the
insulator should not be tied with great force. 
Otherwise, this will damage heat insulation
and causes water condensation.

Connecting the pipe to the indoor unit

Remove the 

fl

 are nut and seal cap.

By loosening the 

fl

 are nut at the pipe end, the refrigerant is discharged in a small amount. 

The arrangement has been made for shipment, and the discharge of refrigerant is never a 
trouble to the equipment.
When the 

fl

 are nut is removed, never fail to remove the seal cap. If not removed, the 

refrigerant will not be circulated, which result the compressor drive motor will possibly be burnt. 
Apply refrigerator oil to the union and the 

fl

 ared portion of the pipe.

Wrap 

fl

 are insulation, bind top and bottom 

fl

 are insulation by binder.

Be sure that the wire is not 
in contact with any metal 
in the wall. Please use 
the protection pipe as wire 
passing through the hollow 
part of the wall so as to 
prevent the possibility of 
damaged by mouse.

!

CAUTION

Connecting of drain pipe

Securely glue connection part of
drain hose and PVC pipe, using PVC 
adhesive.

If gluing of drain hose and PVC pipe
is too weak, water leakage may occur.
Be sure to wrap generally-available
insulator (10mm or more of foamed
polyethylene) around drain hose,
inside the house, for insulation heat.

Checking drain and water leakage.
Perform after connecting power.

If checking of drainage is omitted,
water drop may occur.

Add water to water pan of indoor unit 
as shown below.

Perform test running of drain pump
to check drainage operation.

Test run method

1

  Turn OFF power supply.

2

  Remove cover of electric box and 

set the drain pump test run switch 
to TEST.

3

  After checking the drainage, return 

the switch to NORMAL.

  Connecting the pipe

4

INDOOR UNIT

FOR SERVICE PERSONNEL ONLY

Pattern paper for positioning 
plate

Screw for holder of Remote 
Controller

AAA Size Battery

Binder

Insulation pipe for drain pipe

Insulation pipe

Remote Controller

Pattern paper for installation 
plate

Installation plate 

fi

 xing  screw

(M5 X 16)

4

1

2

2

1

1

1

1

1

4

Blower cover

2

Preparation for installing indoor unit

2

Installation of suspension bolts

 

Be sure to reinforce furring of ceiling (frame : ceiling joints and supporter) to maintain level
of ceiling and prevent vibration of ceiling plate.

 

Suspension bolts should be purchased in the 

fi

 eld.

 

Refer to diagrams shown below for length of suspension bolts.

 

In case of wooden frame

 

In case of steel frame

(Unit : mm)

Be sure to use protection pipe 
(commercial product).
If connecting cables are touching 
metal lath inside the wall or inside 
the wall is hollow where mouse 
can bite cables, it can cause 
electrical shock or 

fi

 re.

If sealing is not complete, high 
humid air from inside the wall or 
outside of the room can come in 
and cause water dripping.

!

WARNING

Drain pipe installation

Use PVC pipe VP20 (O.D. 26mm) for drain pipe.

Be sure to roll an insulation (thickness 10mm or more) for the drain pipe at indoor side.

Always draw the drain pipe downward so that water 

fl

 ows smoothly. Fix it (ex. by hanger)

to prevent a peak and trap.

Installation of indoor unit

3

!

CAUTION

Since 2-way outlet as shown below causes performance problems, do not set it.

Blower cover installation

Install the blower cover only to the air outlet direction which is not in use.
Install the blower cover at the diffuser position shown. Fix the blower cover certainly.

Corner seal installation

Install the corner seal at position shown. Fix the corner seal certainly. Shall be installed 
disregard to 2 directions, 3 directions or 4 directions. 

!

CAUTION

When connecting pipes, if 

fl

 are nut is over-tightened at the small diameter side, the screw 

thread of the service valve may be broken making pipe connection impossible. Be sure to 
tighten the nut with speci

fi

 ed  torque.

If drain pump test run is right
set to TEST, drain pump may
malfunction.

!

CAUTION

The indoor piping 
should be insulated 
with the enclosed 
insulation pipe. (If the 
insulator is insuf

fi

 cient, 

please use commercial 
products).

The difference in height
between the indoor and
outdoor unit should be kept
below 10m.

The connecting pipe, no
matter big or small, should
all be insulated with insulation 
pipe and then wrapped with
vinyl tape. (The insulator will
deteriorate if it is not wrapped 
with tape).

Drain Pipe
Must be installed separately.
Insulate indoor part of pipe to 
prevent condensation.

Be sure to 
completely 
seal any 
gap with 
putty.

Drawing of bottom view of ceiling

Be sure to install the indoor unit level. If the indoor unit is
inclined, water may leak.

If space between bottom surfaces of indoor unit and ceiling
is not correct, there may be a gap between the panel and
indoor unit, with consequence dropping of condensed water.

!

CAUTION

Selecting the switch

1

  Turn OFF power supply.

2

  Remove cover of the electrical box.

3

  When selecting discharge direction of 2 directions or 3 directions, select 

the “AIR FLOW SELECTION” on the main PWB to 3 way.

When selecting discharge direction of 4 directions, select the “AIR FLOW 
SELECTION” on the switch PWB to NORMAL.

NOTE:

During 2 directions or 3 directions, sound level will increase.

3

Corner Seal

Be sure that bottom face
of indoor main unit is the
same height (or expected
height if the ceiling is new 
construction.) as lower
surface of the ceiling.

Selecting the switch

1

  Turn OFF power supply.

2

  Remove cover of the electrical box.

3

  When install the indoor unit 2500mm or 

more from the 

fl

 oor, select the “STATIC 

PRESSURE” switch on the main PWB 
to HIGH pressure.

When install the indoor unit below 
than 2500mm from the 

fl

 oor,  select 

the “STATIC PRESSURE” switch on 
the main PWB to NORMAL.

If constructing the ceiling after installation 
of air conditioner, be sure to attach a
pattern paper for installation that shows
ceiling opening dimension.

<

IA1171: A 

>

Holder for Remote Controller

RAI-25QPB
RAI-35QPB
RAI-50QPB

!

CAUTION

The installation height of indoor

unit must be 2.3m ~ 3m.

1

2

3

4

5

6

7

8

11

12

13

14

16

Qty

No.

Item

1

Insulator

RAI-50RPA

17

 

Set nut and washer on suspension bolt and hook it to suspension clamp by lifting the
indoor unit.

 

Suspension bolt must have play of 20-30 mm on its right and left. If cannot have enough
play, 

fi

 x lifting lug to suspension bolt without attaching nut underneath the suspension bolt,

then attach nut and install indoor unit.

 

Make sure that indoor unit is kept level using a level.

The space between bottom surfaces of ceiling and indoor unit

 

Be sure to install the indoor units as follow position (1).

 

Do not install the indoor units as follows position (2) (3).

(1) Same level (draw in 0~2mm) 

(2) Stick out above 0mm  (3) Draw in above 3mm

Selecting the Mounting Position

The installation place is very important for the air conditioner because it is very dif

fi

 cult  to 

move from one place to another after the 

fi

 rst  installation.

Decide the mounting position together with the customer.
The discharge direction can be selected as shown below.

INS RAI-25-35-50QPB-EN1   1

INS RAI-25-35-50QPB-EN1   1

12/24/14   2:05 PM

12/24/14   2:05 PM