THE CHOICE OF MOUNTING SITE

 (Please note the following matters and obtain permission from customer before installation).

WARNING

!

 The unit should be mounted at stable, non-vibratory location 

which can provide full support to the unit.

WARNING

  The outdoor unit must be mounted at a location which can support 

heavy weight. Otherwise, noise and vibration will increase.

No nearby heat source and no obstruction near the air outlet is allowed.

  The clearance distances from top, right and left are speci

fi

 ed in 

fi

 gure 

below.

  The location must be convenient for water drainage and pipe connection 

with the outdoor unit.

  To avoid interference from noise please place the unit and its remote 

controller at least 1m from the radio, television and inverter type 

fl

 uorescent  lamp.

 To avoid any error in signal transmission from the remote controller, 

please put the controller far away from high-frequency machines and 
high-power wireless systems.

 The installation height of indoor unit must be 2.3m or more.

INDOOR UNIT

Figure showing the Installation of Indoor and Outdoor Unit.

OUTDOOR UNIT

Direction of Piping

There are 6 directions  allowed, 
namely, horizontally perpendicular 
to the unit, vertically down from 
right, horizontally out from right, 
horizontally out to left,
horizontally out to right, vertically 
down from left.
Don’t form the piping downward at 
the left of the unit.

Screw for Mounting Plate

( 4 . 1 x 3 2 )

Names of Indoor Components

Screw for holder of 
Remote Controller

( 3 . 1 x 1 6 )

AAA Size Battery

Holder for Remote 
Controller

Mounting Plate

Qty

No.

Component’s Name

1

6

1

2

2

Remote Controller

Purifying Filter

1

2

3

4

5

6

7

1

2

<

IA1890: B 

>

Installation of Hanger, Wall Penetration and Installation of Protection Pipe

1

CAUTION

!

  The draining of the water container inside the indoor unit can be done from the left. 

Therefore the mounting plate must be 

fi

 xed horizontally or slightly tilted towards the 

side of drain hose. Otherwise, condensed water may over

fl

 ow the water container.

Direct Mounting On The Wall

 Please use hidden beams in the wall to hold the mounting plate.

Wall Penetration and Installation of Protection Pipe

 Drill a ø 65mm hole on 

wall which is slightly tilted 
towards the outdoor side. 
Drill the wall at a small 
angle.

 Cut the protection pipe 

according to the wall 
thickness.

 Empty gap in the sleeve 

of protection pipe should 
be completely sealed with 
putty to avoid dripping of 
rain water into the room.

INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION

The refrigerating pipes should be adjusted to 

fi

 t into the 

hole on the wall and then ready for further connection.

  The terminals of 2 connected pipes must be covered with 

insulator used for terminal connection. Then the pipes 
are wrapped with insulation pipe.

 Connect the connecting cord after removing electrical 

cover. (Refer to “CONNECTION OF POWER CORD”)

 After adjustment, 

fi

 t the connecting cord and pipes into 

the space available under the indoor unit. 

 When connection is at left side, refrigerating pipe and 

cabinet shall be tied together.

  Failing to do so may cause the unit bottom side become 

warping.

  Excess binder shall be cut to prevent abnormal sound 

and water dripping.

THE CONNECTION OF REFRIGERATING PIPE DURING THE 
INSTALLATION OF INDOOR UNIT

Preparation To Install Refrigerating Pipes

Please 

fi

 x in the plastic core 

after 

fl

 aring to avoid copper 

chips entering the pipes.

CAUTION

!

You are free to choose the side (left or right) for the installation of drain 
hose. Please ensure the smooth 

fl

 ow of condensed water of the Indoor 

unit during installation. (Carelessness may result in water leakage.)

!

CAUTION

Be sure that the 
drain hose is not 
loosely connected 
or bend.

Be sure that the wire is not 
in contact with any metal 
in the wall. Please use 
the protection pipe as wire 
passing through the hollow 
part of the wall so as to 
prevent the possibility of 
damaged by mouse.
Unless it seals completely, 
any air with high humidity 
flows from outdoor and 
dew may drop.

!

WARNING

 The refrigerating pipes and connecting cord 

arrangement are attached.

 The end of the refrigerating pipes are at locations 

marked with “ 

” symbol.

   Installation of Drain Hose

3

INDOOR UNIT

Heat insulation pipe

Connecting
cord

Refrigerating pipe

Pull this to the front 
during the connection 
of refrigerating pipes 
to ease task.

Procedures of Installation and Precautions

 Procedures to 

fi

 x the mounting plate.

1. Drill holes on wall.  2. Push plug into the holes.  3. Fix the mounting plate on wall
  (As shown below) 

  (As shown below) 

  with 4.1 x 32 screw

    

   

  (As shown in 

fi

 gure  below)

 Procedures to 

fi

 x the holder of remote control.

1. Drill holes on wall. 

2. Push plug into the holes.

  (As shown below) 

  (As shown below)

   Installation of the Indoor Unit

2

VERTICALLY DOWNWARD PIPING

Preparation

 Connect connecting cord.

 Pull out the pipe, connecting cord and drain hose.

Installation

 The upper part of the indoor unit is hanged on the mounting plate.

 The projection at the lower part of the indoor unit is hooked onto the mounting plate.

Please pull the lower part of 
the indoor unit outwards to 
check if the unit is hooked 
onto the mounting plate. 
Improper installation may 
cause vibration and noise.

!

CAUTION

HORIZONTAL PIPING

Preparation

Change of Drain Hose and Installation Procedures.

Exchange the location of drain hose and drain cap during horizontal piping as shown in 

fi

 gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.

 Please use pliers to pull 

out the drain cap.

  (This is an easier way to 

remove the drain cap).

Dimension of Mounting Stand

of the outdoor unit

(unit : mm)

 

 The difference in height 

between the indoor and 
outdoor unit should be 
kept max 20m.

 The connecting pipe, 

no matter big or small, 
should all be insulated 
with insulation pipe and 
then wrapped with plastic 
tape. (The insulator will 
deteriorate if it is not 
wrapped with tape).

The connection of insulated 
drain hose.

Please use insulated drain 
hose for the indoor piping 
(commercial product).

The indoor piping 
should be insulated 
with the enclosed 
insulation pipe. (If the 
insulator is insuf

fi

 cient, 

please use commercial 
products).

Be sure to 
completely 
seal any 
gap with 
putty.

HOW TO REMOVE INDOOR UNIT

  Push up the (PUSH) sections at the bottom of the indoor unit and 

pull the bottom plate towards you. Then the claws are released from 
the stationary plate.

 

(The (PUSH) sections are indicated by 2 arrows in the right 

fi

 gure)

Installation

Hang the Indoor unit onto the mounting plate. Use the temporary 
stand at the back of the Indoor unit to push its lower part 
15cm forwards.

 Place the drain hose through the hole on the wall.

 Wrap the refrigerating pipes with insulation pipe after 

connecting refrigerating pipe.

 Connect the connecting cord after removing electrical cover. 

(Refer to “Connection of Power Cord”)

 After adjustment, the connecting cord and refrigerating pipes 

are placed into the space available under the Indoor unit.

  The projection of Indoor unit must hook to the mounting plate.

!

!

 Selecting the installation location: Suitable location that will reduce the 

impact from rain and direct sun that may affect the unit performance. 
Besides that, ventillation must be good and clear of obstruction.

  The air blown out of the unit should not point directly to animals or plants.

  The clearances of the unit from top, left, right, front and back are speci

fi

 ed 

in 

fi

 gure below. At least 3 of the above sides must be open air.

 Be sure that the hot air blown out of the unit and noise do not disturb 

the neighbourhood.

  Do not install at a location where there is 

fl

 ammable gas, steam, oil and 

smoke.

 The location must be convenient for water drainage.

  Place the outdoor unit and its connection wire at least 1m away from the 

antenna or signal line of television, radio or telephone. This is to avoid 
noise interference.

 Do not install outdoor unit facing strong wind direction. It may damage 

the fan motor.

   

Do not install the outdoor unit in a place where small animals may build 
their nests. If small animal goes inside the unit and touches the electrical 
parts, failure of the unit, smoke or 

fi

 re may be caused. Request your 

customer to keep the surrounding of the unit is clean.

!

CAUTION

Condensed water may leak out if not 
inserted properly.

Remove the cap for 
drain hose installation

Drain cap

Drain cap shall 
be fully tightened 
by pushing with 
Hexagonal wrench 
key when changing 
location.

!

Protection pipe

Drain hose

Connecting cord

Connected section

Hook

Projection

about 15cm

below 
5mm

Please bend at a small 
radius to form an arc

Binder

Insulation pipe (must be wrapped with vinyl tape at every 120mm).

Drain 
hose

Connecting 
cord

Pipe

Connecting cords, 
pipe and drain 
hose must be laid 
together with Vinyl 
tape.

Mounting plate

Drain Hose

Protection 
Pipe

Refrigerating 
Pipe

Connecting Cord

Lift the body 
of the unit 
upwards and 
then force it 
downwards.

Mounting plate

Projection

Level

Mounting 
plate

Hole for pipe

Line

Weight

Mark

Screw for Mounting Plate 

Please use more than 
4 screws.

Plug

Screw

Remote 
Control 
Holder

Wall

Wall

Wall

Mounting plate

Screw

Plug

4.1 x 32 Screw

Ceiling

Indoor

Outdoor

WALL

Sleeve of 
protection pipe

Protection 
pipe

Seal with 
putty

Seal with 
putty

2 ~ 5mm

Drain hose

Please insert until here

Drain hose

Drain hose

Drain cap

[Push] mark positions

Bending upwards

Condensed water pond

Ditch

Condensed 
water pond

Horizontally
perpendicular
to the unit

Connection

mounting stand

above 100mm

above 100mm

above 100mm

2,300mm or more

Plug

above 300mm

above

400mm

must not bend

Maximum pipe length 30m

Minimum pipe length 3m

inner diameter ø 16mm

above 200mm

above 100mm

give clearance 
as wide as 
possible

above 100mm

above 700mm

above 200mm

CAUTION

For horizontally out to right piping

GOOD

For right piping, follow the instruction as below:

  Press the upper side of clamp

  Unfold the pipe to downward slowly.

  Bend the pipe to the right side of chassis.

BAD

Following bending from left to right directly 

could cause damage to pipe.

   

This unit is chargeless up to 30m pipe length.

   

Installation of pipe length less than minimum pipe length 
requirement (3 meters) may generate an abnormal sound.

!

CAUTION

This symbol shows that this equipment 
uses a 

fl

 ammable  refrigerant.

If the refrigerant is leaked, together 
with an external ignition source, there 
is a possibility of ignition.

This symbol shows that the Operation 
Instructions should be read carefully.

This symbol shows that a service 
personnel should be handling this 
equipment with reference to the 
Installation Manual.

This symbol shows that there is 
information included in the Operation 
Manual and/or Installation Manual

WARNING

CAUTION

CAUTION

CAUTION

CAUTION

  A brazed, welded or mechanical 

connection shall be made before 
opening the valves to permit 
refrigerant to 

fl

 ow between the 

refrigerating system parts. A vacuum 
valve shall be provided to evacuate 
the interconnecting pipe and/or any 
uncharged refrigerating system.

  Mechanical connectors used indoor 

shall comply with ISO 14903. 
When mechanical connectors are 
reused indoors, sealing parts shall 
be renewed. When 

fl

 are joints are 

reused indoors, the 

fl

 are part shall 

be re-frabricated.

  Refrigerant tubing shall be protected 

or enclosed to avoid damage.

!

RAC-PH30HLT

––

1.60kg

Model

Maximum

charge R32

Additional 

R32

1.60kg

2.44m

2

30m

Factory 

charge R32

Indoor

A

min

 (m

2

)

Chargeless 

up to

SAFETY PRECAUTION

  Read the safety precautions carefully before operating the unit.

  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

  

WARNING ........ Incorrect methods of installation may cause death or serious injury.

  

CAUTION ......... Improper installation may result in serious consequence.

 

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating 
the unit as described in the user’s guide.

Tools Needed For Installation Work

  Flare nut must use a torque wrench without fail. Tighten with the speci

fi

 ed  tightening  torque. 

If the 

fl

 are nut is tightened too much, after a long period of time, the 

fl

 are nut breaks, Gas 

leakage, stagnation, touching 

fi

 re, rarely cause ignition.

  Sharp bending of the pipe use the polyethylene rod, bend not crushed the pipe. Gas leakage 

from the crushed part, stagnation, touching 

fi

 re, rarely cause ignition.

  Please request your sales agent or quali

fi

 ed technician to install your unit. Water leakage, 

short circuit or 

fi

 re may occur if you do the installation work yourself.

  Please observe the instructions stated in the installation manual during the process of 

installation. Improper installation may cause water leakage, electric shock and 

fi

 re.

  Make sure that the units are mounted at locations which are able to provide full support to 

the weight of the units. If not, the units may collapse and impose danger.

  Please ensure smooth 

fl

 ow of water when installing the drain hose.

  Piping shall be suitable supported with a maximum spacing of 1m between the 

supports. 

  Please use the speci

fi

 ed components for installation work. Otherwise, the units may collapse 

or water leakage, electric shock and 

fi

 re may occur.

  Be sure to use the speci

fi

 ed piping set for R32. Otherwise, this may result in broken copper 

pipes or faults.

  When installing or removing an air conditioner, only speci

fi

 ed refrigerant (R32) shall be 

allowed, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure 
in the refrigeration cycle may become abnormally high so that a rupture may be caused.

  Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes 

into contact with 

fi

 re, a poisonous gas may occur. Be aware that refrigerants may not contain 

an odour.

  After completion of installation work, check to make sure that there is no refrigeration gas 

leakage. If the refrigerant gas leaks into the room, coming into contact with 

fi

 re in the fan-

driven heater, space heater, etc., a poisonous gas may occur.

 Unauthorized modi

fi

 cations to the air conditioner may be dangerous. If a breakdown occurs 

please call a quali

fi

 ed air conditioner technician or electrician. Improper repairs may result 

in water leakage, electric shock and 

fi

 re,  etc.

   Must install air conditioner according to the electrical installation standards for Thailand of 

the Engineering Institue of Thailand under The Royal Patronage of His Majesty (the King).

  A circuit breaker must be installed. Without a circuit breaker or fuse the danger of electric 

shock exists.

  The external switch shall be incorporated to completely disconnect from power supply. It 

should disconnect all poles, and a contact separation of at least 3mm must be present.

  Do not install the unit near a location where there is 

fl

 ammable gas. The outdoor unit may 

catch 

fi

 re  if 

 

fl

 ammable gas leaks around it.

   

Do not install the indoor unit in a machine shop or kitchen where vapor from oil or its mist 

fl

 ows to the indoor unit. The oil will deposit on the heat exchanger, thereby reducing the 

indoor unit performance and may deform and in the worst case, break the plastic parts of 
the indoor unit.

  Please ensure smooth 

fl

 ow of water when installing the drain hose.

  Piping shall be suitable supported with a maximum spacing of 1m between the supports.

!
!

CAUTION

!

WARNING

!

Carefully read through the procedures of 
proper installation before starting installation 
work.

 The sales agent should inform customers 

regarding the correct operation of installation.

 mark is tool exclusive use for R32)

 +   –  Screwdriver 

   

Measuring Tape 

   

 Knife   

 Saw  

 Pipe Cutter  

 Hexagonal Wrench Key (

 4mm)

 Power Drill (ø 65mm ~ ø 80mm)   

 Vacuum Pump   

 Pliers or Wrench   

 Torque Wrench 

 Vacuum Pump Adaptor   

 Flare Tool    

 Gas Leakage Detector

 Manifold Valve 

       

 Charge Hose  

  

<IA1890:  B  >

INSTALLATION

MANUAL

SPLIT UNIT AIR CONDITIONER

INDOOR UNIT

RAS-PH30HLT

OUTDOOR UNIT

RAC-PH30HLT

EN

 INSTRUCTION MANUAL

FOR SERVICE 
PERSONNEL ONLY

CAUTION

CAUTION

CAUTION

 The rubber strap used for 

fi

 xing the insulator should 

not be tied with great force. 
Otherwise, this will damage 
heat insulation and causes 
water condensation.

Rubber strap tied
with great force

Pipe

!

CAUTION

!