IA669: A 

>

!

THE CHOICE OF MOUNTING SITE 

(Please note the following matters and obtain permission from customer before installation).

WARNING

!

O

 

The unit should be mounted at stable, non-vibratory location which can 
provide full support to the unit.

WARNING

!

O

 

The Outdoor unit must be mounted at a location which can support heavy weight. 
Otherwise, noise and vibration will increase.

!

O

No nearby heat source and no obstruction near the air outlet is allowed.

O

  The clearance distances from top, right and left are speci ed in  gure below.

O

  The location must be convenient for water drainage and pipe connection with 

the Outdoor unit.

O

  To avoid interference from noise please place the unit and its remote controller 

at least 1m from the radio, television and inverter type  uorescent  lamp.

O

  To avoid any error in signal transmission from the remote controller, please put 

the controller far away from high-frequency machines and high-power wireless 
systems.

O

  The installation height of indoor unit must be 2.3m or more.

CAUTION

!

O

  Do not expose the unit under direct sunshine or rain. Besides, ventilation must be 

good and clear of obstruction.

O

  The air blown out of the unit should not point directly to animals or plants.

O

 The clearances of the unit from top, left, right and front are speci ed in  gure 

below. At least 3 of the above sides must be open air.

O

 Be sure that the hot air blown out of the unit and noise do not disturb the 

neighbourhood.

O

  Do not install at a location where there is  ammable gas, steam, oil and smoke.

O

  The location must be convenient for water drainage.

O

  Place the Outdoor unit and its connecting cord at least 1m away from the antenna 

or signal line of television, radio or telephone. This is to avoid noise interference.

O

 Do not install outdoor unit facing strong wind direction. It may damage the fan 

motor.

INDOOR UNIT

OUTDOOR UNIT

CAUTION

!

!

Other optional parts for display panel 
& wireless remote control SPX-RCK4

Display panel

Panel installation plate

Panel cover

Remote controller 
(wireless)

Holder for remote control

3.1 x 16 screw

Item

Quantity

No.

1

2

3

4

5

6

1

1

1

1

1

2

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

HITACHI CEILING CASSETTE-UNIT AIR  

CONDITIONER INSTALLATION MANUAL

Maximum pipe length 50m

Minimum pipe length 5m

Above 100mm

give clearance
as wide as 
possible

Above 200mm

Above 50mm when 
installed on the
ceiling of balcony

Above 200mm

Above 100mm

Above 500mm

Air
outlet

Air
outlet

1000 mm
or more

1000 mm
or more

Air inlet

300 mm or more

Air
outlet

Air
outlet

1000 mm
or more

1000 mm
or more

Air inlet

2500 mm or more

O

Carefully read through the procedures of proper installation 
before starting installation work.

O

The sales agent should inform customers regarding the correct 
operation of installation.

FOR SERVICE PERSONNEL ONLY

Tools Needed For Installation Work

O

   

+  –  

Screwdriver  

O

 Measuring Tape  

O

 Knife  

O

  Saw    

O

 ø 65mm Power Drill   

O

 Hexagonal Wrench Key (    4mm)      

O

Wrench (14,17,19,22,26,27mm)  

O

 Gas Leakage Detector 

O

Pipe Cutter  

O

 Vinyl Tape  

O

Pliers  

O

 Flare Tool 

O

 

Read the safety precautions carefully before operating the unit.

O

  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING ........ Incorrect methods of installation may cause death or serious injury.

CAUTION ......... Improper installation may result in serious consequence.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as 
described in the user’s guide.

WARNING

O

 

Please request your sales agent or quali ed technician ti install your unit. Water leakage, sort circuit or  re may occur if you do the 
installtion work yourself.

O

 

Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause 
water leakage, electric shock and  re.

O

 

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units 
may collapse and impose danger.

O

 

Observe the rules and regulations of the electrical installtion and the methods described in the installation manual when dealing 
with the electrical work. Use power cables approved by the authorities of your country.

O

 

Be sure to use speci ed wire for the connection indoor and outdoor units. Please ensure that the connections are tight after the 
conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and  re.

O

 

Please use the speci ed components for installtion work. Otherwise, the units may collapse or water leakege, electric shock and 
 re may occur.

O

 

Be sure to use the speci ed piping set for R-22. Otherwise, this may result in broken copper pipes or faults.

O

 

When installing or removing an air conditioner, only speci ed refrigerant (R-22) shall be allowed, do not allow air or moisture to 
remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may 
be caused.

O

 

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with  re, a poisonous gas 
may occur.

O

 

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into 
the room, coming into contact with  re in the fan-driven heater, space heater, etc., a poisonuos gas may occur.

O

 

Unauthorized modi cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali ed air conditoner 
technician or electrician. Improper repairs may result in water leakage, electric shock and  re,  etc.

O

 

A circuit breaker or fuse (20A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3.5mm has to be installed in the power supply line to the outdoor unit.

O

 

Piping shall be suitable supported with a maximum spacing of 1m between the supports.

O

 

Do not install the unit near a location where there is  ammable gas. The outdoor unit may catch  re if 
 ammable gas leaks around it.

O

 

For installation of front panel RAI-ZCPM, please follow exactly the instruction in the manual.

O

 

Please ensure smooth  ow of water when installing the drain hose.

Paper Pattern
(Carton Board)

Names of Indoor Components

Level Scaler 
(Cut and Take
Out it from the
Carton Board)

Cross Recessed
Head Screws (M6)

Washer with Insulation
Material (M10)

Washer (M10)

Drain Hose

Hose Clamp

Insulation (22iD)

Insulation (28ID)

Cord Clamp

Packing
(5Tx50x200)

Cord Clamp

Remote Controller

Packing
(5Tx270x270)

Screw for holder of 
Remote Controller

Figure showing the installation of Indoor Unit

CAUTION

CAUTION

The installtion 
height of indoor 
unit must be 2.3m 
or more.

In case the pipe lenght is more than 5m, add refrigerant 
R22 at 35 gram per every meter exceeds. However, 
pipe lenght shall not exceed 50m.

Be sure to 
completely 
seal any 
gap with 
putty. 

The indoor piping should be 
insulated with the enclosed 
insulation pipe. (If the 
insulator is insuf cient, please 
use commercial products).

O

  The difference in 

height between the 
indoor and outdoor 
unit should be kept 
below 30m.

O

  The connecting 

pipe, no matter big 
or small, should 
all be insulated 
with insulation pipe 
and then wrapped 
with vinyl tape. 
(The insulator will 
deteriorate if it is 
not wrapped with 
tape).

Drain Pipe 
Must be installed 
seperately. 
Insulate indoor part 
of pipe to prevent 
condensation.

Bush

Bush

Drain Pipe

Dimension of Mounting Stand 

of the outdoor unit

Mounting Stand

(unit : mm)

Opening of False Ceiling and Suspension Bolts

Dimension of Opening

860 to 910

(Dimension of 

Suspension Bolts)

4-Positions of
Suspension Bolts

Dimension of Opening

860 to 910

(Dimension of 

Suspension Bolts)

840 (Unit Size)

Air Panel

Drain Piping
Connection Side

Piping Connection 
Side

Fig. 1 Opening of False Ceiling and Suspension Bolts

(1)  Determine the  nal location and installation direction of the indoor unit 

paying careful attention to the space for the piping, wiring and maintenance.

(2)  Cut out the area for the indoor unit in the false ceiling and install suspension      

bolts, as shown in Fig. 1.

(3)  Check to ensure that the ceiling is horizontally level, otherwise drainage 

can not  ow.

(4)  Strengthen the opening parts of the false ceiling.
(5)  Mount suspension bolts, as shown in Fig. 2

* For Concrete Slab

* For Steel Beam

150 to 160mm

Insert 
(100 to 150kg)

Concrete

Anchor Bolt

(W3/8 or M10)

I Beam

Suspension Bolt
(W3/8 or M10)

Fig. 2  Mounting the Suspension Bolts

Mounting Position of the Indoor Unit

4-Suspension Bolts
M10 or W3/8 (Field-Supplied)

Surface of 
Ceiling

W-Nut (Field Supplied)

Washer (Accessary)

10 Min.

* indicates the dimension between lower face of

indoor unit and surface of ceiling.

Fig. 3   Mounting Position

Liquid Pipe Connection

Drain Pipe Connection

1

18 (Drain Pipe)

(for Cable)

(Liquid Pipe Connection)

(Gas Pipe Connection)

Gas Pipe Connection

Wiring Hole (ø 32.5 Hole)

 (for Spare)

Wiring Hole (30x30)

Fig. 4   Indoor Unit and Air Panel

Mounting the Indoor Unit

(1)  Mounting the nuts and washers to the suspension bolts.

Suspension Bolt (Field Supplied)

Nut (Field Supplied)

 4  *Washer with Insulation (Accessary)

Suspension Blacket (Attaced Indoor Unit)

 5 *Washer (Accessary)

Nut (Field Supplied)

 Surface of Ceiling

Approx. 52

 Approx. 

50

Fig. 5  Mounting Nuts and Washers

* Put the washer so that the surface with insulation can faces downwards.

(2)  Lift the Indoor Unit by hoist, and do not put any force on the drain pan.
(3)  Secure the indoor unit using the nuts, washers.

Suspension Bolt

Suspension Bracket

Drain Pan

Fig. 6   Mounting the Indoor Unit

NOTE

If a false ceiling has already benn installed, complete all piping and wiring work               
inside the ceiling before hooking-up the indoor unit.

Adjusting the Space between Indoor Unit and False Ceiling Opening

CAUTION

O

Check the level of the drain pan using a water level to avoid incorrect opera-

tion of the drain discharge mechanism in the indoor unit. The drain piping 
side of the indoor unit must be approximately 5mm lower than the other part. 

O

Tighten the nuts of the suspension brackets after the adjustment is completed. 

Apply LOCK-TIGHT paint* to the bolts and nuts in order to prevent them 
from loosening. If not done, abnormal noises or sounds may occur and the 
indoor unit may fall down.

LOCK-TIGHT paint*: Paint the lock bolts and nuts. Adjust the indoor unit to the                
correct position while checking with the checking scales (factory-supplied).

(1)  Pattern Board for installation is printed on the packing.

Cut off the checking scale for dimension of opening from packing.

Checking Scale for  
Dimension of Opening

Packing 
(Corrugated Board)

Pattern Board
for installation

(2)  Adjust the position of indoor unit, as shown below by using checking scale.

Indoor Unit (Viewed from Bottom Side)

Surface of Flange

Surface of Ceiling

Indoor Unit

Slub

10 to 35

10 to 35

10 to 35

10 to 35

(a)  For Ceiling already Completed with Panels

Attach the scale to the 
bottom side of the unit

Attach the scale to the 
face of ceiling

Checking Scale for 
Dimension of Opening

Adjust the height of the ceiling 
and the unit at each corner.

Check the dimension of opening 
at each side

(b)  Ceiling Not Completed with Panels yet

Pattern Paper 
for Installation

Dimension for 
Opening

Dimension for 
Opening

Suspension Bolt

Indoor unit

Screw (M6)  

Surface of Ceiling

Pattern Board 
for Installation

Installation Details for Air Panel

O

The details of installation work for air panel shall be according to the Instal-
lation Manual for Air Panel.

O

Check to ensure that the connection of connectors between the indoor unit 
and the air panel.

Names of Outdoor Components

No.

Qty

Item

INDOOR UNIT

(EN) INS RCI-30MH1 (4).indd   1

7/19/10   11:33 AM

Summary of Contents for RAC-30MH1

Page 1: ...circuit breaker or fuse the danger of electric shock exists A main switch with a contact gap of more than 3 5mm has to be installed in the power supply line to the outdoor unit O Piping shall be suitable supported with a maximum spacing of 1m between the supports O Do not install the unit near a location where there is ammable gas The outdoor unit may catch re if ammable gas leaks around it O For ...

Page 2: ...e drain piping pour another 1 5 to 2 0 liters of water into the drain D Switch ON the power supply and press the RUN STOP button CAUTION O In case of pouring water through the access door O In case of pouring water through the air outlet 1 The position of the drain pipe connection is shown in Fig 6 1 Fig 6 1 Position of Drain Pipe Connection 2 Prepare a polyvinyl chloride pipe with a 32mm outer di...

Page 3: ...nnector Wall recessed wiring installation Supplied 0 50 gap Inside top wiring installation Alternative Wires Wires Lead wires 3 strands Lead wires connector Wiring installation illustrations When the wires to be connected from the inside top portion of top casing 1 Break off a perforated aperture located at the top portion of the bottom casing by nipper Smoothen the aperture by cutter 2 Fix the bo...

Page 4: ...the band put the connecting cords in the band and snap it Loose the band put the connecting cords in the band and snap it Connecting cords Removal Of Air From The Pipe And Gas Leakage Inspection Gas Leakage Inspection Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right If gas leakage occurs further tighten the connection to stop leakage P...

Reviews: