9 Servicing
KPI-(252-2002)(E/X)4E - Energy recovery and active energy recovery ventilation units
SMGB0099 rev.0 - 12/2016
337
9
5
Draw out the air filters (2 pieces) which are located at the bottom of the heat exchanger elements.
9.11.6
Removal of the float switch (X4E series only)
1 Remove the 4 screw from the service cover (a) situated
closed the SA duct connector and remove the service
cover.
2 Float switch is on the bottom left side, close de service
window.
3
Unscrew the nut on the float switch and remove from its
bracket.
4 Unplug the connector that is inside the protection cap
and take out the float switch.