3 Piping work and refrigerant charge
Refrigerant and drain hose installation
SMGB0099 rev.0 - 12/2016
125
3
Kit installation:
Drain pump
Drain hose
Drain pan
Fan cover 1
Fan cover 2
Maximum water head height in case of units with drain pump (-DU models or units with drain up mechanism kit).
1/25~1/100
Down slope
Max.
850 mm
RPIM
Indoor unit
3.5.11 RPK-(0.6-4.0)FSN(H)3M - Wall type
Refrigerant pipe installation
Gas pipe connection
The position of the gas pipe connection is possible in all directions (above, left or right).
Model
Measurements (mm)
a
b
c
g
RPK-(0.6-1.0)FSN(H)3M
395
107
288
243
RPK–1.5FSN(H)3M
395
107
288
262
RPK-(2.0-4.0)FSN3M
480
141
339
471
50R
b
a
g
c
Insulation
Left rear side hole
for pipe and wire
Refrigerant gas pipe
For rear side piping
Exterior contour
for indoor unit
For right side piping
Liquid pipe connection
Model
Measurements (mm)
d
e
f
h
RPK-(0.6-1.0)FSN(H)3M
450
107
343
188
RPK–1.5FSN(H)3M
450
107
343
207
RPK-(2.0-4.0)FSN3M
540
141
399
418
50R
e
d
h
f
Left rear side hole
for pipe and wire
Insulation
Refrigerant liquid pipe
Exterior contour
for indoor unit
For right side piping
For rear side piping