3.2 Copper pipes, sizes, connection and insulation
3.2.1 Copper pipes and sizes
C A U T I O N
•
The copper pipe used in the refrigeration installations is different to the copper pipe used in installations
carrying domestic or heating water.
•
The copper pipe for refrigeration installations is especially treated for outdoors and indoors. The interior
surface finish makes it easier for the gas refrigerant to circulate and withstands the action of the lubricant oil
applied to outdoor equipment.
Prepare the copper pipes provided by the supplier.
Select the pipe with the appropriate diameter and thickness. Use the table below to select the most appropriate pipe:
Nominal diameter
Thickness mm
Supply
mm
Inches
Ø6.35
1/4
0.80
Roll
Ø9.53
3/8
0.80
Roll
Ø12.7
1/2
0.80
Roll
Ø15.88
5/8
1.00
Roll
Ø19.05
3/4
1.00
Pipe
Ø22.20
7/8
1.00
Pipe
Ø25.40
1
1.00
Pipe
Ø28.60
1-1/8
1.00
Pipe
Always use clean copper pipes with no signs of knocks or cracks. Make sure there is no dust or dampness on the inside.
Before you install the pipes, clean the inside with oxygen-free nitrogen gas to eliminate any remains of dust or other
substances.
C A U T I O N
•
Do not use hand saws, circular saws, abrasive grinders or other tools that generate shavings.
•
Strictly follow national or local regulations regarding occupational health and safety.
•
Wear appropriate means of protection during cutting or brazing operations and installation (gloves, eye
protection, etc).
On completing the installation of the gas refrigerant pipes -B-,
insulate them appropriately using suitable insulating material -A-
and seal the open space between the holes made and the pipe, as
shown in the figure.
3 Piping work and
refrigerant charge
79
SMGB0063 rev. 1 - 10/2010
3
Summary of Contents for Econofresh
Page 2: ......
Page 4: ...Index ii SMGB0063 rev 1 10 2010 ...
Page 12: ...Index x SMGB0063 rev 1 10 2010 ...
Page 24: ...1 General information 12 SMGB0063 rev 1 10 2010 ...
Page 88: ...2 Unit installation 76 SMGB0063 rev 1 10 2010 ...
Page 169: ... KPI 3002H2E heat recovery unit 4 Electrical wiring 157 SMGB0063 rev 1 10 2010 4 ...
Page 170: ...4 Electrical wiring 158 SMGB0063 rev 1 10 2010 ...
Page 192: ...5 Control system 180 SMGB0063 rev 1 10 2010 ...
Page 234: ...6 Optional functions 222 SMGB0063 rev 1 10 2010 ...
Page 252: ...9 1 RCD 1 0 3 0 FSN2 9 Spare parts 240 SMGB0063 rev 1 10 2010 ...
Page 254: ...9 2 RCD 4 0 5 0 FSN2 9 Spare parts 242 SMGB0063 rev 1 10 2010 ...
Page 256: ...9 3 RPC 4 0 6 0 FSN2E 9 Spare parts 244 SMGB0063 rev 1 10 2010 ...
Page 258: ...9 4 RPI 0 8 1 5 FSNE 9 Spare parts 246 SMGB0063 rev 1 10 2010 ...
Page 260: ...9 5 RPI 8 0 10 0 FSN2E 9 Spare parts 248 SMGB0063 rev 1 10 2010 ...
Page 262: ...9 6 RPIM 0 8 1 5 FSNE DU 9 Spare parts 250 SMGB0063 rev 1 10 2010 ...
Page 264: ...9 7 RPK 1 0 1 5 FSN2E 9 Spare parts 252 SMGB0063 rev 1 10 2010 ...
Page 268: ...9 9 RPK 2 0 FSN2E 9 Spare parts 256 SMGB0063 rev 1 10 2010 ...
Page 270: ...9 10 RPK 2 5 4 0 FSN2E 9 Spare parts 258 SMGB0063 rev 1 10 2010 ...
Page 272: ...9 11 RPF 1 0 2 5 FSN2E 9 Spare parts 260 SMGB0063 rev 1 10 2010 ...
Page 274: ...9 12 RPFI 1 0 2 5 FSN2E 9 Spare parts 262 SMGB0063 rev 1 10 2010 ...
Page 276: ...9 Spare parts 264 SMGB0063 rev 1 10 2010 ...
Page 407: ......