Replacing a Host I/O Board or Host I/O Module
10–5
Hitachi Unified Storage Hardware Service Guide
Replacing a Host I/O Module on a CBL Controller Box
To replace a Host I/O Module on CBL Controller Boxes:
1. Loosen one blue screw that secures the Host I/O Module, and then pull
the lever open. When the lever is opened completely, the Host I/O
Module can be removed.
2. Pull out and remove the Host I/O Module.
3. Place the removed Host I/O Module in a temporary location where anti-
static measures are observed.
4. Wait at least 30 seconds, and then install the new Host I/O Module. If
you insert the Host I/O Module without waiting at least 30 seconds, the
controller might not recover normally. If this occurs, remove the inserted
Host I/O Module from the storage system, wait at least 30 seconds and
then re-insert it into the storage system.
5. Push the Host I/O Module into the slot, with its levers opened
completely.
6. Close the lever and tighten the blue screw you loosened earlier to secure
the Host I/O Module.
7. Be sure the red STATUS LED on the Host I/O Module goes OFF and the
orange WARNING LED on the front side of the Controller Box is OFF.
8. Be sure the orange WARNING LED on the front side of the Controller
Box is OFF. If it blinks slowly, visit the HDS Support Portal at
The controller usually recovers in about three minutes;
however, if the I/O load from the host computer is high, it may take
about 30 minutes to recover.
9. Connect all the cables you removed.
10.Confirm that the green READY LED on the front of the Controller Box is
ON. This LED might blink quickly for 40-to-60 minutes or 80-to-180
minutes when the DBW is connected to the CBL before the LED goes ON.
11.In Storage Navigator Modular 2, check the recovery after replacing
components (see
Checking recovery after replacing components on
).
NOTE: When connecting Fibre Channel interface cables, insert the cables
until they are securely connected to the host connectors. If the Fibre
Channel interface cables are inserted half way into the host connectors, the
controller detects Fibre Channel failures and I/O processing can deteriorate
Summary of Contents for CBL
Page 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Page 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Page 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Page 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Page 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Page 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Page 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Page 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Page 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Page 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Page 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Page 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Page 291: ...1 Hitachi Unified Storage Hardware Service Guide ...