17
EN
3.2.3 Switch Setting Procedures
Change switch setting before turning on.
Switch setting is as follows. Factory default setting may need to be changed depending on use
in the field.
Table 3.3 Switch Settings
Switch
Mode Setting
Factory
Setting
Remarks
DS1 (4-position DSW)
Pin No. DHCP Mode
Static Mode
Restore Factory
Setting
1
ON
ON
OFF
ON
Do NOT set other patterns.
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
ON
4
OFF
OFF
ON
OFF
DS3 (2-position DSW)
1
ON: The second protection fuse for H-LINK is
active
OFF: The second protection fuse for H-LINK is
inactive
OFF
When the first protection
fuse for H-LINK is blown,
set 2 pin on DS3 to ON to
make short-circuit between
fuse terminals.
2
ON: H-LINK Terminal Resistance is active
OFF: H-LINK Terminal Resistance is inactive
OFF
Ensure that no other
terminal resistance exists
on the same H-LINK
when activating terminal
resistance from the
airCloud Gateway.
NOTE:
● DHCP mode is the factory default setting.
At last, align the top cover to the guide plate (dent) on the bottom cover to reattach the top
cover upon completing wiring work.
Install the screw
in the direction
of the arrow
Screw
Hook
Hook the top dip
hook and install
the top cover
Figure 3.12 Attaching Top Cover
Summary of Contents for airCloud HC-IOTGW
Page 34: ... airCloud Gateway 空調機管理系統 安裝 維護手冊 型號 HC IOTGW ...
Page 62: ...CN MEMO ...