(5) Follow the instruction below to perform power wiring work.
Table 3.2 Connecting Wires
Type of Wiring
Power Line
Power Input
AC 100~240V 50/60Hz
Wiring Length
-
Cable Specification
AWG15(1.5mm
2
) to AWG12(2mm
2
)
Outer diameter finish is up to 10mm
Terminals/Connector
M3 Screw Terminal
Connection Procedure
Crimping Pliers
Cable
Cable
Terminal
Line pressing board
15mm
10mm
Φ6-Φ8.5mm
Screw Tightening Torque: 0.25 N·m
Screw Tightening Torque: 0.5 N·m
Terminal
1. Let wire out of the power line outlet.
2. Insert wire into round terminal.
3. Crimp the round terminal to fix wire.
4. Fix each round terminal to terminals with screw.
5. Fix cable with line pressing board.
Type of Wiring
H-LINK (Communication Line)
LAN Cable
Specification
5VDC
IEEE802.3 Compliant
100BASE-TX/10BASE-T
Wiring Length
Less than 1,000m (3,281ft.)
Less than 100m (328.1ft.)
Cable Specification
AWG21 (0.75mm
2
) to AWG16 (1.25mm
2
)
LAN Cable (CAT 5 or more)
Terminals/Connector
M2.5 Screw Terminal
RJ45 Connector
Connection Procedure
Screw Tightening Torque:
0.4N·m
Non-polar
▪ Crimp the round terminal to connect wire.
▪ Let wire out of H-LINK line outlet.
▪ Fix each round terminal to terminals with screw.
▪ Let wire out of LAN wire outlet.
▪ Insert connector until lock sound is heard.
NOTE:
● The distance between the power line and communication line is more than 150mm.