3 Servicing
Cycle components
SMGB0120 rev.0 - 11/2017
76
3.3.20
Replacement of the thermistor (Evaporation, THMe)
1
Cut and remove the plastic bands that fixes
the insulation of the discharge pipe thermistor
(THMe).
2
Loosen the screw fixing the thermistor.
3
At the E-box, disconnect the CN26TD contact
(or the Faston terminals 9 and 10 of multiple
contact QCN3)
4
Remove the thermistor.
5
When reassembling after replacing the
thermistor (THMe), perform the procedure in
the reverse order than removing.
Thermistor
THMe
Evaporation
pipe
Thermistor THMe
Screw
Plastic bands
3.3.21
Replacement of the thermistor (Cooler water inlet, THMwi)
1
Unscrew the nut of the cable gland
2
Gently pull the sensor wiring upwards.
!
C A U T I O N
Sensor sheath is full of sealing silicone. Use gloves
and eye goggles for protection in order to avoid
possible injuries to eyes and skin.
3
Disconnect the 3 and 1 Faston terminals or
the CN5 connector at the E-box
4
Replace the thermistor in reverse order than
removing.
?
N O T E
Use sealant silicone inside the sensor sheath to
protect and avoid any leakage.
Thermistor (THMwi)
Cable gland
Fitting adaptor Sensor sheath
Sensor
Sensor wiring