Be sure to satisfy the max.high distance &max.pipe length at the same time when do the refrigerant piping design 
and installation.

Max.High 

Distance

High Distance between Outdoor and 
Indoor Unit

Outdoor is Higher than Indoor Unit

 D1

<

30m

Indoor is Higher than Outdoor Unit

 D1

<

20m

Max.High Distance between Indoor and Indoor 

 D2

<

8m

Max.Pipe 

Length

Max.Length between Indoor and outdoor 

 L1

<

40m

Max.Length between branch valve box and outdoor 

 L2

<

30m

Max.Length between branch valve box and indoor 

 L7

<

20m

Total Pipe length

 L2

+

L3

+

L4

+

L5

+

L6

+

L7

<

100m

Total refrigerant charge:TOTAL WEIGHT<2.0kg 

( 

calculted in the following formula.If the calculated additional coolant amount more than 2.0kg, should 

reduce the length of the pipe line.

Refrigerant  Additional Charge
The unit has been filled with refrigerant, but need additional charge for all the connected pipes in the refrigerant system.
Adding additional refrigerant according to the connecting pipe diameter and pipe length. Refrigerant type is 
R410A, additional charge is calculated as follows:
Calculate charge refrigerant quantity by liquid pipe length, charge it to refrigerant cycle.
W1(kg)

L2×0.050kg/m

W2(kg)

=(

L3

+

L4

+

L5

+

L6

+

L7)×0.015kg/m

Total Addtional refrigerant charge W = W1 + W2

MODEL

:

AMW-42U4SE

IMPORTANT

CAREFULLY READ THIS MANUAL  BEFORE INSTALLATION, AND FOLLOW 
THE INSTRUCTIONS TO INSTALL.
PLEASE HAND THIS MANUAL TO THE USER AFTER INSTALLATION.
PLEASE COOPERATE WITH INDOOR UNIT MANUAL BEFORE USING.

.

KEEP THIS MANUAL FOR

 

FUTURE

 

REFERENCE

室外机安装前请确认包装箱内附件有以下部件:

Transport the product as close to the installation location as practical before unpacking.

Check accessories

Transportation and Handling

 

before

 

Installation

Outdoor Installation

Refrigerant Piping 

SELECTING THE INSTALLATION LOCATION

AIR CONDITIONER

 

INSTALLATION

 

MANUAL

 

1.

This air conditioner uses new refrigerant

 HFC(R410A)

.

 

2.

Since the max. working pressure is 4.15MPa(R22:3.1MPa),some of the piping and installation and service tools are special.

 

3.

This air conditioner unit should be connected with the branch box or special indoor unit, allowed models please  consult the 

      sales staff before installation .

 

4

.

This air conditioner uses power

 

supply

:

220V

-240V

,50Hz

.

·

Be sure to use a dedicated power circuit, and do not put other loads on the power supply.

·

Be sure to read these SAFETY PRECAUTIONS carefully before installation.

·

Be sure to comply with SAFETY PRECAUTIONS of installation manual, because it contains

    important safety issues. Definitions for identifying hazard levels are provide below with their respective safety symbols.

 

     

WARNING

Hazards or unsafe practices which COULD result in severe personal injury or death.

         

CAUTION

: 

Hazards or unsafe practices which COULD result in minor personal injury or product or puoperty damage.

         

CAUTION

·

Please carefully file indoor and outdoor unit  manual away for future reference.

·

Installation should be left to the professional ,do not do it by yourself(customer).

    Incomplete installation could cause damage  by fire, electric shock, drop or water leakage .
    Please consult your dealer or professional installation personnel.

·

Install the air conditioner on a solid base that can support the unit weight.

    An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.

·

Use the specified type of wires for electrical connections safely between the indoor and outdoor units.

    And firmly connected to the connection part of wire terminals , so that the wire stress will not be applied to these parts. 
    Incomplete connection may cause fire.

·

For wiring, use a cable long enough to cover the entire distance with no connection.  

    And don't connect multiple devices to the same AC power supply.
   Otherwise, it may  be due to bad contact, poor insulation, exceed the allowable current and cause a fire or electric shock.  

·

After all installation is complete,  check to make sure that no refrigerant is leaking out.

   If the refrigerant gas leakage to the interior, and the heater, stove flame touching it, will generate harmful substances.

·

Perform the installation securely referring to the installation manual.

    Incomplete installation could cause a personal  injury due to fire, electric shock, the unit falling or leakage of water.

·

In accordance with the installation instructions for electrical work, please be sure to use a dedicated line.

·

If the power supply circuit capacity or electrical work is not in place, may cause a fire or electric shock.

·

Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely.

·

If the electrical cover in the indoor unit or the service panel in the outdoor unit are not attached securely, it could result in  a fire or 

    an electric shock due to dust water, etc.

   

·

Please be sure to cut off the main power supply before the installation of indoor electronic PCB or wiring .

    Otherwise it will cause electric shock.

·

The device should be in accordance with the state provisions for installation wiring.

·

The indoor appliance should be placed not in the children's height -- at least above ground 2.5m.

·

The outdoor machine installation location should pay attention to the protection, avoid people or other small animals contact with electrical

     components, please keep the outdoor unit of the surrounding environment clean and tidy.

·

When installing or relocating the unit, make sure that no substance other than the specified refrigerant(R410A) enters the refrigerant circuit.

    Any presence of foreign substance such as air can cause abnormal pressure rise or an explosion.

    

·

Perform earthing

   Do not connect the earth wire to a gas pipe, water pipe, lightning rod or telephone earth wire. 
   Defective earthing could cause an  electric shock.

·

Do not install the unit in a place where an inflammable gas leaks.

    If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.

·

Fasten a flare nut with torque wrench as specified in this manual.

    When fastened too tight, a flare nut may break after a long period and cause a leakage of refrigerant.

·

Install an earth leakage breaker depending on the installation place(where it is humid). 

    If a earth leakage breaker is not installed, it could cause an electric shock.

·

Perform the drainage/piping work securely according to the installation manual.

·

If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.

·

Hanging Method

  

When hanging the unit, ensure a balance of the unit, check 

   safety and lift up smoothly.

 (

1

Do not remove any packing materials.

 (

2

Hang the unit under packing condition with two ropes, 

          as shown in Fig. blow.

·

Hanging

 

If have no package to move,Please protect with

   cloth or paper.

·

Where it is not exposed to strong wind.                                 

·

Where airflow is good and clean.

·

Where it is not exposed to rain and direct sunshine.

·

Where neighbors are not annoyed by operation sound or hot air.

·

Where rigid wall or support is available to prevent the increase of operation sound or vibration.

·

Where there is no risk of combustible gas leakage.

·

Where it is at least 3m away from the antenna of TV set or radio. An amplifier may be required for the affected device.

·

Install the unit horizontally.

·

Please install it in an area not affected by snowfall or blowing snow. In areas with heavy snow, please install a canopy, a pedestal   

   and/or some baffle boards. 

Before choosing the installation site, obtain user approval.

    
  

Avoid the following places for installation where air conditioner trouble is liable to occur.

·

Where there is much machine oil.

·

Salty places such as seaside.

·

Where sulfide gas is generated such as a hot spring.

·

Where there is high-frequency or wireless equipment.

Note:
When operating the air conditioner in low outside temperature, be sure to follow the instruction describe below.

·

Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind.

·

To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.

·

To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.

 

FREE SPACE REQUIRED AROUND OUTDOOR UNIT(Unit:mm)

Before connect with outdoor and indoor/ branch box, DO  confirm the maximum allowed length of pipeline

.

 

Obstacles

When there is an obstacle around the outdoor unit, it does not matter if the position of the obstacle  as shown in the figures below.

·

When installing the unit in an area that is enclosed on four sides such as a verandah, be sure to leave move than 200mm behind the unit .

·

When there is a lack of airflow or there is a possibility of becoming short cycle, install an outlet guide and make sure there is enough  space 

   behind the rear side of the air inlet.
NOTE:
Make sure not to install several outdoor units sideways next to each other.

Refrigerant piping is short, the better. So the connecting pipe should be as short as possible.

·

Be sure to fix the unit’s legs with bolts when installing it.

·

Be sure to install the unit firmly to ensure that it does not fall  by earthquake or gust.

·

The anchor bolts, nuts and washers for the installation areuser prepared

.

NOTE

NOTE:This figure is based on the external view of a standard model.
   Consequently, the shape may differ from that of the  air conditioner you have selected.

 

Pipe out direction, can be connected

 with indoor unit or branch box.

4X? d

unit

:mm

Outdoor Unit Model

Capacity(KBtu/h)

A

B

C

D

E

d

42

580

380

410

340

70

15

Ф

1

2

4

5

3

WARNING

C

AUTION

Check the following accessories are included with the unit before installation

INSTALLATION MANUAL

1piece

5

-

1

 

Piping

 

Requirement

1

2

Please read these SAFETY PRECAUTIONS carefully to ensure correct installation

.

Put

 

Cloth

 

or

 

Paper

100 or more

500 or more

100 or more

350 or more

200 or more

500 or more

100 or more

500 or more

Blowing guide

(1).Obstacle  over the top side.

(2).Obstacle in three direction(bu top 
      side is open) .

(3).Obstacle on front(blowing)
      side only. In this case, the
      rear, both side and top sh-
      ould be open.

(4).Obstacle on front and rear side 
      only. The unit can be used by 
      attaching an optional outdoor
      blowing guide(but both sides and
      top are open).

(5).Service space
      Keep the service space as shown
      in the figure below for maintenance

100 or more

500 or more

100 or more

500 or more

350 or more

Service space

M10

 Max.

21mm

Air

 

Flow

 

Direction

Anchor

 

Bolt

Base

 

of

 

Outdoor

 

Unit

Nut

Special

 

Washer

Filled

 

Mortar

 

Concrete

*Cut

 

the

 

portion

 

when

 

this

 

type of

 

anchor

 

bolt

 

is

 

used

If

 

not

it

 

is

 

difficult

 

to

 

remove the

 

service

 

cover

.

 

of

 

Outdoor

 

Unit

Outer

 

Diameter

 

of

 

Pipe 

Outer

 

Diameter

 

of

 

Pipe

 

            

G

as                             Liquid

Diameter

(

KBtu

/

h

)

42

9.52

   

 

BRANCH BOX

INDOOR UNIT1

INDOOR UNIT2

INDOOR UNIT3

INDOOR UNIT4

INDOOR UNIT5

OUTDOOR UNIT

L3

L4

L5

L6

L7

D2

L1

D1

L2

Summary of Contents for AMW-42U4SE

Page 1: ...ment clean and tidy When installing or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any presence of foreign substance such...

Page 2: ...bration of the piping Pay special attention in case of short piping length 3 Tightening the flare nut use two spanners like figure right 4 Apply the refrigerant oil filed supply thinly at the seat sur...

Page 3: ...Garantire il rispetto delle PRECAUZIONI DI SICUREZZA del manuale d installazione perch contiene importanti nozioni sui problemi legati alla sicurezza Le definizioni per l identificazione dei livelli...

Page 4: ...rante allo stato liquido attraverso la valvola di arresto del liquido Alla fine si prega di chiudere le valvole e registrare la quantit di carica di refrigerante La carica di refrigerante preimpostata...

Page 5: ...alaci n ya que contiene cuestiones importantes sobre la seguridad Las definiciones para identificar los niveles de peligros est n provistas debajo con sus respectivos s mbolos de seguridad ADVERTENCIA...

Page 6: ...entador de c rter Comprobar que el interruptor en la fuente el ctrica principal est ENCENDIDO por m s de 6 horas en el precalentamiento De lo contrario se puede da ar el compresor Apague el suministro...

Page 7: ...nta o dedicada e n o coloque outras cargas no fornecimento de energia Certifique se de ler estas PRECAU ES DE SEGURAN A antes da instala o Certifique se de cumprir com as PRECAU ES DE SEGURAN A do man...

Page 8: ...rimeiro descarregue o ar da mangueira de carga e em seguida abra as v lvulas carregue o refrigerante como o tipo l quido por meio da v lvula de bloqueio de l quido Finalmente feche as v lvulas e regis...

Reviews: