44
Setting Wiring Mode and Configuring Current Sensor Settings
Representative values of current sensor phase characteristics
See the table below for information about the current sensor phase characteristics.
Model name
Frequency (kHz)
Representative value of
phase difference between
input and output (
°
)
CT6841
100.0
−1.82
CT6843
100.0
−1.68
CT6844
50.0
−1.29
CT6845
20.0
−0.62
CT6846
20.0
−1.89
CT6862
300.0
−10.96
CT6863
100.0
−4.60
CT6865
1.0
−1.21
CT6875
200.0
−10.45
CT6875-01
200.0
−12.87
CT6876
200.0
−12.96
CT6876-01
200.0
−14.34
CT6877
100.0
−2.63
CT6877-01
100.0
−3.34
CT6904
300.0
−9.82
9709
20.0
−1.11
PW9100
300.0
−2.80
For all current sensors, the values are representative ones under the following conditions.
•
Standard cable length (not using the extension cable)
•
With the conductor positioned at the center of the sensor
For the phase characteristics information when using CT9557, contact your authorized Hioki
distributor or reseller.
HIOKI PW8001A961-00
Summary of Contents for PW8001-01
Page 2: ...HIOKI PW8001A961 00...
Page 6: ...Contents iv HIOKI PW8001A961 00...
Page 56: ...50 Checking Connections HIOKI PW8001A961 00...
Page 120: ...114 Power Calculation Method HIOKI PW8001A961 00...
Page 162: ...156 Controlling Integration with External Signals HIOKI PW8001A961 00...
Page 236: ...230 U7005 15MS s Input Unit HIOKI PW8001A961 00...
Page 258: ...252 Index HIOKI PW8001A961 00...
Page 259: ...HIOKI PW8001A961 00...
Page 260: ...HIOKI PW8001A961 00...
Page 261: ...HIOKI PW8001A961 00...
Page 262: ...www hioki com HIOKI PW8001A961 00...