Chapter V Basic Operation Instructions
110
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
setting of
auxiliary
frequency Y
frequency
F1.06
Maximum
output
frequency
Upper limit frequency
~
650.00Hz
0.01Hz 50.00Hz
×
F1.07
Main
frequency x
digital
setting
Lower limit frequency ~ upper limit
frequency
0.01Hz 50.00Hz
○
F1.09
Upper limit
frequency
Lower limit frequency ~ maximum output
frequency
0.01Hz 50.00Hz
○
F1.10
Lower limit
frequency 0.00~upper limit frequency
0.01Hz
0.00Hz
○
5.4 Analog input
The HAV-SP series is configured with 2 analog input terminals (AI1 and AI2 are of
0~10V/0~20mA input, Al1 can select voltage input or current input through jumper J1, and AI2 can
select voltage input or current input through jumper J2) and 1 high-speed pulse input terminal. Each
input can be filtered independently, and be adjusted. The corresponding input curve can be set by
setting the input corresponding to the maximum and minimum values.
Related parameter table:
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
F5.00
AI1
minimum
value
0.00
~
F5.02
0.01V
0.00V
○
F5.01
Set value
correspondin
g to AI1
minimum
value
-100.0%
~
100.0%
0.1%
0.0%
○