4 Start-up
X-MIO 7/6 01
Page 56 of 72
HI 801 305 E Rev. 5.00
4.5.12
Diagnostic Status [DWORD]
Coding of the variable
Diagnostic Status
.
ID
Description
0
Diagnostic values are indicated consecutively.
100 Bit-coded
temperature
status
0 = normal
Bit0 = 1 : Temperature threshold 1 has been exceeded
Bit1 = 1 : Temperature threshold 2 has been exceeded
Bit2 = 1 : Fault in temperature measurement
101
Measured temperature (10 000 digits/ °C)
200
Bit-coded voltage status
0 = normal
Bit0 = 1 : L1+ (24 V) is faulty
Bit1 = 1 : L2+ (24 V) is faulty
201
202
203
Not used!
300
Value of 24 VDC power supply is below 24 V (BOOL)
1001…1003 Channel status of the measuring inputs 1...3, I/O unit: = 0
Coding
Description
0x0001
Fault occurred in hardware unit (submodule).
0x0100
Channel fault, defective supply status
0x0800
No value exists for the rotation sense
0x1000
The process values cannot be created
0x2000
Edge distance error
0x8000
Warning: Only two of the sampled input values are
error-free and available for the 2oo3 evaluation
1101…1103 Channel status supply, measuring inputs 1...3, I/O unit: = 1
Coding
Description
0x0001
Fault occurred in hardware unit (submodule).
0x0010 Short-circuit
detected
0x0020 Open-circuit
detected
0x0100
Channel fault, defective supply status
0x0200
Line monitoring fault occurred
0x0400
Low or overvoltage (supply)