3 Product Description
X-MIO 7/6 01
Page 32 of 72
HI 801 305 E Rev. 5.00
3.7
System Cable
The following system cables are necessary for cable plugs X1 and X2:
Cable plug
System cable
X1, left cable plug (Figure 7)
X-CA 005
X2, right cable plug (Figure 7)
X-CA 008
Table 21: Necessary System Cables
3.7.1
System Cable X-CA 005
The X-CA 005 system cable is used to wire the X-CB 018 04/07 connector boards
(cable plug X1) to the field termination assemblies.
General
Cable
LIYCY-TP 38 x 2 x 0.25 mm²
Wire
Finely stranded
Average outer diameter (d)
approx. 16.8 mm
Minimum bending radius
Fixed laying
Flexible application
5 x d
10 x d
Combustion behavior
Flame resistant and self-extinguishing in
accordance with IEC 60332-1-2, -2-2
Length 8…30
m
Color coding
Based on DIN 47100, see Table 19.
Table 22: Cable Data X-CA 005
Identical Cable Plugs
Figure 8: System Cable X-CA 005 01 n