3 Product Description
X-MIO 7/6 01
Page 24 of 72
HI 801 305 E Rev. 5.00
Digital outputs
Number of outputs (number of channels)
5, unipolar with ground L-,
non-galvanically isolated
Output voltage
≥
L+ minus internal voltage drop
Voltage drop (with high level)
2.2 V at 2 A output current
Nominal rated current (with high level)
1.6 A, range 0.01...2 A
Total permissible current
12 A
Leakage current (with low level)
max. 1 mA
Current limiting in the event of short-circuit
approx. 4.33 A, each channel
Ohmic load
Up to nom. rated current 2 A
Inductive load
max. 10 H
Capacitive load
Inrush current of max. 3 A for t < 2.5 s
SC threshold
3.3 A for t > 6 ms
2.1 A for t > 2.5 s
Overload protection of the outputs,
transient
33 V (max. 43 V)
Switching time of the channels (with ohmic
load)
≤
100 µs
Test pulse (with ohmic load)
typ. 250 µs
Behavior upon overload
The affected output is switched off and cyclically
switched on again
Table 13: Specifications for the Digital Outputs
Relay Output
Number of outputs (channels) 1,
potential-free,
non-safety-related
Switching voltage
5...30 V
Switching current
1...180 mA
Switching frequency
max. 250 Hz
Switching time
(energized contact closed)
4 ms
Reset time (de-energized contact
closed, without wiring)
4 ms
Bounce time for the energized contact
2 ms
Contact material
AgNi + Au
Life time
Mechanical
Electrical
≥
10 x 10
8
switching operations
≥
2 x 10
5
switching operations with ohmic full load
Table 14: Product Data for the Relay Output