background image

HI 800 417 BEA 

 

HIMatrix H 7033 

 

9 of 10 

1.4 

Mounting the H7033 in Zone 2 

(EC Directive 94/9/EC, ATEX) 
 
If the special conditions X are observed, the H 7033 device may be installed in Zone 2.  
The corresponding EC declaration of conformity is available on the HIMA website. 
 

Special Conditions X 

Mount the device in an enclousure (cabinet) that meets the EN / IEC 60079-15 requirements 
and achieves a type of protection of at least IP54 (category 1) in accordance to 
EN / IEC 60529. 
This enclosure (control cabinet) must be labelled as follows: 
 

WARNUNG – NICHT UNTER SPANNUNG ÖFFNEN 

WARNING – DO NOT OPEN WHEN ENERGIZED 

 
 

Note

If a potentially explosive atmosphere has been precluded, work can be also 
performed when the device is under voltage. 

 

 

The enclosure (control cabinet) in use must be able to safely dissipate the generated heat. 
The H 7033 device has a power dissipation of 

9

 W

.  

 
Since the device is equipped with exchangeable fuses, an additional warning must be placed 
on the front plate of the enclosure (control cabinet). The warning should have following text: 
 

WARNUNG – 

SICHERUNGEN NICHT UNTER SPANNUNG 
HERAUSNEHMEN ODER WECHSELN 

WARNING – 

DO NOT REMOVE OR REPLACE FUSES  
WHEN ENERGIZED 

 

 
The EC Directives and the following standards must be observed when installing and 
operating the device: 
 

DIN EN 60079-15 (VDE 0170/0171 Part 16) 
DIN EN 60079-0 (VDE0170-1) 
DIN EN 60079-11 (VDE0170-7) 
DIN EN 60079-14 (VDE 0165 Part 1) 

 
The H 7033 device is labelled with the following special product marking: 

 

µ

 II 3 G Ex nA II T4 X

     

0°C 

 Ta 

 60°C

 

 

S p e c i a l   c o n d i t i o n s   X   m u s t  b e  r e g a r d e d !

 

 

 

 

 

Summary of Contents for HIMatrix H 7033

Page 1: ...Industrial Automation HIMatrix System Manual H 7033 Three Wire Transmitter Supply HIMA Paul Hildebrandt GmbH Co KG Industrial Automation HI 800 417 BEA...

Page 2: ...validity However we cannot fully preclude flaws or typesetting errors in this manual For this reason HIMA offers no warranties and assumes no legal responsibilities or liabilities for the potential c...

Page 3: ...Supply H 7033 4 1 1 Introduction 4 1 1 1 Terminal Description for H 7033 5 1 1 2 PIN Assignment for Three Wire Transmitter Supply 6 1 2 Operation 7 1 2 1 Monitoring of the Transmitter Supply Voltage U...

Page 4: ...of the HIMatrix F60 and supplies the connected three wire transmitters with external supply voltage H 7033 has the following characteristics It protects the MI 24 01 inputs 8 external transmitter supp...

Page 5: ...t 1 5 mm SM Monitoring of transmitter supply voltage UTM connection on the MI 24 01 analog input 2 5 mm L Ground Connection on the MI 24 01 ground 2 5 mm IMI1 IMI8 Series connection unit analog output...

Page 6: ...6 IMIH1 34 INT1 7 I 35 S 8 IMI2 36 S2 9 IMIH2 37 INT2 10 I 38 S 11 IMI3 39 S3 12 IMIH3 40 INT3 13 I 41 S 14 IMI4 42 S4 15 IMIH4 43 INT4 16 I 44 S 17 IMI5 45 S5 18 IMIH5 46 INT5 19 I 47 S 20 IMI6 48 S6...

Page 7: ...tage UTM To monitor the transmitter supply voltage UTM connect the analog input of the MI 24 01 module to the SM and L terminals The transmitter supply voltage UTM is monitored via the current IMI24 s...

Page 8: ...onitoring of the transmitter supply voltage SM Monitored transmitter supply voltage UTM UTM UTmin IT x Rwire UFuse 500 mA Tolerance Fuse G fuse cartridge 500 mA Part no 57 0174059 Filter Time constant...

Page 9: ...be also performed when the device is under voltage The enclosure control cabinet in use must be able to safely dissipate the generated heat The H 7033 device has a power dissipation of 9 W Since the...

Page 10: ...HIMA the safe decision HIMA Paul Hildebrandt GmbH Co KG Industrial Automation P O Box 1261 68777 Br hl Telephone 49 6202 709 0 Fax 49 6202 709 107 1043 E mail info hima com Internet www hima com...

Reviews: