System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 59 of 114
Read-only in RUN
After starting the controller, no operating action
such as stop, start or download is permitted in
SILworX , except for forcing and reload.
FALSE
Application-
specific
Relay Contact 1
...Relay Contact 4
Only applicable with F60!
It controls the corresponding relay contacts, if
existing.
FALSE
Application-
specific
Reload Deactivation Only applicable with F*03!
It prevents the controller from being by performing
a reload.
FALSE
Application-
specific
User LED 1
...User LED 2
Only applicable with F*03!
It controls the corresponding LED, if existing.
FALSE
Application-
specific
Table 29: Hardware System Variables - CPU OS V7 and Higher
Global variables can be connected to these system variables; the value of the global variables is
modified using a physical input or the user program logic.
7.3.1.4
Hardware System Variables for Reading the Parameters
These system variables can be accessed in the SILworX Hardware Editor.
Select the gray background outside the (yellow) subrack representation and double-click or use
the context menu to open the Detail View.
Variable
Description
Data
Type
Number of Field Errors
Number of current I/O errors
UDINT
Number of Field Errors -
Historic Count
Counted number of I/O errors (counter resettable)
UDINT
Number of Field Warnings
Number of current I/O warnings
UDINT
Number of Field Warnings -
Historic Count
Counted number of I/O warnings (counter resettable)
UDINT
Communication Error Count
Number of current communication errors
UDINT
Communication Error Historic
Count
Counted number of communication errors (counter resettable)
UDINT
Communication Warning
Count
Number of current communication warnings
UDINT
Communication Warnings
Historic Count
Counted number of communication warnings (counter resettable) UDINT
System Error Count
Number of current system errors
UDINT
System Error Historic Count
Counted number of system errors (counter resettable)
UDINT
System Warning Count
Number of current system warnings
UDINT
System Warning Historic
Count
Counted number of system warnings (counter resettable)
UDINT
Autostart
ON:
When the processor system is connected to the supply
voltage, it automatically starts the user program
BOOL
OFF: When the processor system is connected to the supply
voltage, it enters the STOP state
OS Major
Operating system version contained in processor system
UINT
OS Minor
UINT
CRC
Resource configuration checksum
UDINT
Date/time [ms portion]
System date and time in s and ms since 1970-01-01
UDINT
Date/time [s portion]
UDINT